RS-422 and RS-232C Cable

2-1

Power Supply and Cable Lengths

Power Supply
Cable Lengths
Caution
!
2-2

RS-422 and RS-232C Cable

6
For all but AL001 Link Adapters, connect the AC hot line to the common terminal
of the Link Adapter. A fuse is internally connected to the common line.
Maximum length for RS-232C cable is 15 m. For RS-422 it is 500 m, with a maxi-
mum of 10 m for any given branch line. For RS-485 cable it is 200 m.
Maximum lengths for optical fiber cables connected to Link Adapters are deter-
mined by the type of cable and the particular model of Link Adapter employed.
Link Adapters whose model numbers are followed by "-P" can be connected to
either APF (all-plastic optical fiber) or PCF (plastic-clad optical fiber) cable.
Those without "-P" can be connected only to PCF cable. The model numbers,
cable types, and transmission distances are related as follows:
Cable
Model No. With P
APF
20 m
PCF
200 m
If transmission distances over 800 meters are required, it is necessary to use
AGF (crystal optical fiber) cable, which calls for the use of specific Link Adapters
(see 1-4 General Specifications ). For calculating maximum length for AGF
cable, see 2-4 Crystal Optical Fiber Cable (AGF ).
Never use a Link Adapter with its terminal cover removed. Keep the cover se-
curely attached. If the Link Adapter is installed in an office or on a desk, take ex-
tra care to avoid electrical shock.
When using optical fiber or RS-422 cable, it is possible to connect several Host
Link Units to one host computer. When RS-232C cable is used, however, the
connection must either be on a one-to-one basis or a Link Adapter must be used
to convert to optical or RS-422 cable. As described below, wiring will vary de-
pending on whether a Host Link Unit is connected directly to a host computer or
whether it is connected indirectly through a Link Adapter.
When a Host Link Unit is connected one-to-one to a host computer, with no Link
Adapter, and RS-232C cable is being used, connect the SD (send data) terminal
of the host computer to the RD (receive data) terminal of the Host Link Unit. Like-
wise, connect the RD terminal of the host computer to the SD terminal of the
Host Link Unit. When using RS-422 cable, the SDA and RDA terminals and the
SDB and RDB terminals should be connected in a similar way. The following dia-
gram illustrates the proper connections when using RS-232C cable.
Host computer
1
FG
7
SG
2
SD
3
RD
Pin No. Symbol
Model No. Without P
Not connectable
800 m
Section
2-2
Host Link Unit
FG
1
SG
7
SD
2
RD
3
Symbol Pin No.