Controls And Display; Master Switch; Led Display - Kohler 8.5RES Service

Table of Contents

Advertisement

5.2 Controls and Display

The ADC-RES controller has an LED display and a
three-button keypad. See Figure 5-2. The DC-RET
controller has an LED display. See Figure 5-3.
A three-position generator set master switch is mounted
on the controller junction box.
1
2

1. LED display

2. Select button (use for setup and adjustment only)
3. Up and down arrow buttons (use for setup and adjustment only)
4. Generator set master switch (RUN--OFF/RESET-AUTO)
Figure 5-2 ADC-RES Controller
5.2.1

Master Switch

The generator set master switch is a three-position
(RUN\OFF/RESET\AUTO)
Figure 5-2 or Figure 5-3 for the master switch location.
See Section 6.15 for master switch connections.
5.2.2
LED Display
The LED display shows runtime hours, fault codes,
application program version number, or controller
parameters during configuration and adjustment. See
Figure 5-4.
54
Section 5 ADC-RES and DC-RET Controller
Downloaded from
www.Manualslib.com
rocker
switch.
manuals search engine
1
3
1. LED display
2. Generator set master switch (RUN--OFF/RESET-AUTO)
Figure 5-3 DC-RET Controller
The LED display is activated by a start or RUN
4
command as follows:
Move the master switch to RUN.
D
GM57149
With the master switch in AUTO, send a remote start
D
command (close the remote start contact across
leads 3 and 4).
The LED display indicates generator set status as
shown in Figure 5-5. When the generator set is running,
engine runtime hours are shown.
When the generator set is running, the arrow keys on the
ADC-RES can be used to step through the other
See
displays as described in Section 5.2.3.
When the master switch is in AUTO, the display turns off
48 hours after generator set shutdown.
2
GM57149
TP-6196 10/09

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

12resm112resnt12tres12res12resl

Table of Contents