HPE 750W Common Slot -48VDC Hot Plug Power Supply (94%
efficiency)
Specification
Input requirements
Rated input voltage
Rated input current
Rated input power (W)
Rated input power (Btus per
hour)
Power supply output
Rated steady-state power (W) 750 W
Maximum peak power (W)
CAUTION: This equipment is designed to permit the connection of the earthed conductor of
the DC supply circuit to the earthing conductor at the equipment.
If this connection is made, all of the following must be met:
• This equipment must be connected directly to the DC supply system earthing electrode
conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC
supply system earthing electrode conductor is connected.
• This equipment must be located in the same immediate area (such as adjacent cabinets) as
any other equipment that has a connection between the earthed conductor of the same DC
supply circuit and the earthing conductor, and also the point of earthing of the DC system.
The DC system must be earthed elsewhere.
• The DC supply source is to be located within the same premises as the equipment.
• Switching or disconnecting devices must not be in the earthed circuit conductor between
the DC source and the point of connection of the earthing electrode conductor.
CAUTION: To reduce the risk of electric shock or energy hazards:
• This equipment must be installed by trained service personnel, as defined by the NEC and
IEC 60950-1, Second Edition, the standard for Safety of Information Technology
Equipment.
• Connect the equipment to a reliably grounded SELV source. An SELV source is a
secondary circuit that is designed so normal and single fault conditions do not cause the
voltages to exceed a safe level (60 V DC).
• The branch circuit overcurrent protection must be rated 24 A.
HPE 1200W Common Slot Platinum Plus Hot Plug Power
Supply (94% efficiency)
Specification
Input requirements
Value
-36 V DC to -72 V DC
-48 V DC nominal input
23 A at -36 V DC input
17 A at -48 V DC input, nominal
input
11 A at -72 V DC input
815 W at -36 V DC input
805 W at -48 V DC input, nominal
input
795 W at -72 V DC input
2780 at -36 V DC input
2740 at -48 V DC input, nominal
input
2720 at -72 V DC input
750 W
Value
Specifications 90