10-4. TROUBLESHOOTING CHECK TABLE
Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after
the power ON), the indoor fan motor turns OFF and OPERATION INDICATOR lamp flashes.
OPERATION INDICATOR
Abnormal
No.
Operation indicator lamp
point
Upper lamp fl ashes.
0.5-second ON
Miswiring
1
or serial
signal
0.5-second OFF
Upper lamp fl ashes.
Indoor coil
2-time fl ash
thermistor
2
Room tem-
perature
2.5-second OFF
thermistor
Upper lamp fl ashes.
3-time fl ash
Indoor fan
3
motor
Upper lamp fl ashes.
4-time fl ash
Indoor con-
4
trol system
Upper lamp fl ashes.
5-time fl ash
Outdoor
5
power sys-
tem
Upper lamp fl ashes.
6-time fl ash
Outdoor
6
thermistors
Upper lamp fl ashes.
7-time fl ash
Outdoor
7
control sys-
tem
Upper lamp fl ashes.
14-time fl ash or more
Other ab-
8
normality
2.5-second OFF
Outdoor
9
control sys-
Upper lamp lights up
tem
OBH647C
Lighted
Blinking
Not lighted
2.5-second OFF
2.5-second OFF
2.5-second OFF
2.5-second OFF
2.5-second OFF
Symptom
The serial signal from the outdoor unit is not
received for 6 minutes.
The indoor coil or the room temperature ther-
mistor is short or open circuit.
The rotational frequency feedback signal is
not emitted during the indoor fan operation.
It cannot properly read data in the nonvolatile
memory of the indoor electronic control P.C.
board.
Indoor unit and
outdoor unit do
not operate.
It consecutively occurs 3 times that the com-
pressor stops for overcurrent protection or
start-up failure protection within 1 minute after
start-up.
The outdoor thermistors short or open circuit
during the compressor operation.
It cannot properly read data in the nonvolatile
memory of the inverter P.C. board or the out-
door electronic control P.C. board.
An abnormality other than above mentioned
is detected.
Outdoor unit
It cannot properly read data in the nonvolatile
does not oper-
memory of the inverter P.C. board or the out-
ate
door electronic control P.C. board.
23
Condition
• Refer to 10-6.
miswiring and serial signal er-
ror".
• Refer to the characteristics of
indoor coil thermistor, and the
room temperature thermistor
(10-7.).
• Refer to 10-6.
indoor fan motor".
• Replace the indoor electronic
control P.C. board.
• Refer to "How to check of in-
verter/compressor".
Refer to outdoor unit service
manual
• Check the stop valve.
• Refer to "Check of outdoor
thermistor".
Refer to outdoor unit service
manual.
• Replace the inverter P.C. board
or the outdoor electronic con-
trol P.C. board.
Refer to outdoor unit service
manual.
• Check the stop valve.
• Check the 4-way valve.
• Confi rm the abnormality in
detail using the failure mode
recall function for outdoor unit.
• Check the blinking pattern of
the LED on the inverter P.C.
board or the outdoor electronic
control P.C. board.
Remedy
"How to check
"Check of