RESETTING THE HEATER CONTROL

Soft lockouts as diagnosed by the system error codes
require the gas control to be reset.
To reset the control, slide the "ON/OFF" switch to the
"OFF" position. Wait for 10 seconds and move the
switch back to the "ON" position.
If the problem that caused the control to lock out has
not been corrected, the control will remain or again go
back into lockout.

LOCKOUTS

Soft Lockout

occurs when a system safety device trips to break the
sequence of operation. The control will retry the system
in a timed basis but will not reinstate operation until the
failure is corrected.

Hard Lockout

occurs when the main controller fails and must be
replaced.
The gas control valve\thermostat includes a temperature
limiting ECO (Energy Cut Off) system that will shut off the
water heater if the water temperature is too high.
Should the water temperature get too high, the diagnostic
status light will indicate a code (4 fl ashes), indicating an
over-temperature condition and the main burner will be
shut off. If a high temperature condition occurs, turn the
main gas supply OFF and have the water heater repaired
by a qualifi ed service technician. Contact your local dealer
for service information.
Note: Should an over-temperature condition occur, restart
the water heater and verify the LED fl ash sequence. If the
4 fl ash sequence is observed, slide the "ON/OFF" switch to
the "OFF" position. Turn Main Gas Supply "OFF". Replace
the gas control valve\thermostat.
48

IGNITION STATE AND TIMING

IGNITION STATE
Pre-purge
Hot Surface Igniter
(HSI) Warmup
Ignition Activation
Period (IAP)
Flame Recognition
Period (FRP)
Trial For Ignition
Flame Stabilization
Period
Inter-purge
Flame Failure
Response Time
Post-purge
Pressure Switch (PS)
Prove Period
Pressure Switch (PS)
Fault Delay (failed
open/closed)
Soft Lockout
Energy Cut Off
(ECO) Limit Lockout
Flammable Vapour
(FV) Sensor Lockout
TIMING
5 seconds (NG models)
15 seconds (LP models)
10 seconds
3.5 seconds maximum
0.5 second
IAP + FRP
Not Applicable
30 seconds
2 seconds max
(@ 1uA fl ame current)
30 seconds
2 minutes
2 minutes
20 minutes
Indefi nite
Indefi nite (see "Resetting The
Heater Control")