Sediment Traps/Dirt Leg - Smith BTF-80 SERIES 210 Installation And Operating Manual

Commercial gas water heaters
Table of Contents

Advertisement

Make sure the gas supplied is the same type listed on
the model rating plate. The inlet gas pressure must not
exceed 14 inch w.c. for natural gas and propane gas. The
minimum inlet gas pressure shown on the rating plate is
that which will permit fi ring at rated input.
All gas piping must comply with local codes and ordinances
or with the current edition of the "Natural Gas and
Propane Installation Code" B149.1 . Copper or brass
tubing and fi ttings (except tin lined copper tubing) should
not be used.
If the gas control valve/thermostat is subjected to
pressures exceeding 1/2 psi, the damage to the gas
control valve/thermostat could result in a fi re or explosion
from leaking gas.
If the main gas line shut-off serving all gas appliances is
used, also turn "OFF" the gas at each appliance. Leave
all gas appliances shut "OFF" until the water heater
installation is complete.
A gas line of suffi cient size must be run to the water
heater. Consult the current edition of the "Natural Gas
and Propane Installation Code" B149.1 and your gas
supplier concerning pipe size.
There must be:
A readily accessible manual shut-off valve in the gas
supply line serving the water heater, and
A sediment trap (dirt leg) ahead of gas control valve/
thermostat to help prevent dirt and foreign materials
from entering the gas control valve/thermostat.
A ground joint union or equivalent means to disconnect
piping between the shut-off valve and gas control valve/
thermostat to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting
the water heater. Use a soapy water solution, not a match
or open fl ame. Repair and retest as required. When
fi nished, rinse off soapy solution and wipe dry.
WARNING
• Use joint compound or tape
compatible with propane.
• Leak test before operating
heater.
• Disconnect gas piping and
shut-off valve before pressure
testing system.
Use pipe joint compound or Tefl on tape marked as being
resistant to the action of gases.
The appliance and its gas connection must be leak tested
before placing the appliance in operation.
The appliance and its individual shut-off valve should be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
331432-00
Fire and Explosion Hazard
excess of 1/2 psi. It should be isolated from the gas supply
piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 psi.
Connecting gas piping to the gas control valve/thermostat
of water heater can be accomplished by the method shown
in Figure 21.
BLACK PIPE
SEDIMENT
76mm
TRAP
(3 in.) MIN.
CAP
Figure 21

SEDIMENT TRAPS/DIRT LEG

WARNING
• Contaminants in gas lines can
• Clean all gas piping before
• Install sediment trap in accor-
Contaminants in the gas lines may cause improper
operation of the gas control valve/thermostat that may
result in fi re or explosion. Before attaching the gas line be
sure that all gas pipe is clean on the inside. To trap any
dirt or foreign material in the gas supply line, a sediment
trap (sometimes called a dirt leg) must be incorporated
in the piping. The sediment trap should be either a tee
fi tting with a capped nipple in the bottom outlet or other
device recognized as an effective sediment trap. If a tee
fi tting is used, it should be installed in conformance with
the method of installation shown in Figure 21. Refer to
the current edition of the "Natural Gas and Propane
Installation Code" B149.1 .
GAS
GROUND
CONTROL
JOINT
VALVE
UNION
(OPTIONAL)
Fire and Explosion Hazard
cause fire or explosion.
installation.
dance with CSA-B149.1.
21

Advertisement

Table of Contents
loading

Related Products for Smith BTF-80 SERIES 210

This manual is also suitable for:

Btf-80 series 211

Table of Contents