Panasonic CS-W18CKP Service Manual page 63

Hide thumbs Also See for CS-W18CKP:
Table of Contents

Advertisement

230V
Indoor wet
30
bulb temp.
TC
SHC
17.0°C
5.26
3.99
19.0°C
19.5°C
5.77
4.17
22.0°C
6.29
4.33
230V
Indoor wet
30
bulb temp.
TC
SHC
17.0°C
6.97
5.29
19.0°C
19.5°C
7.66
5.54
22.0°C
8.34
5.74
TC - Total Cooling Capacity (kW)
SHC - Sensible Heat Capacity (kW)
IP - Input Power (kW)
Outdoor Temp. (°C)
35
IP
TC
SHC
IP
1.51
4.91
3.82
1.63
5.30
1.65
1.54
5.40
4.01
1.66
1.57
5.88
4.16
1.69
Outdoor Temp. (°C)
35
IP
TC
SHC
IP
2.55
6.52
5.07
2.74
7.03
2.78
2.59
7.16
5.32
2.79
2.64
7.80
5.52
2.84
63
CS-W18CKP CU-W18CKP5 / CS-W24CKP CU-W24CKP5
40
TC
SHC
IP
TC
4.57
3.67
1.74
4.16
5.02
3.86
1.77
4.56
5.47
4.01
1.80
4.97
40
TC
SHC
IP
TC
6.06
4.87
2.93
5.51
6.66
5.12
2.99
6.05
7.25
5.33
3.04
6.59
46
SHC
IP
3.49
1.88
3.67
1.91
3.83
1.95
46
SHC
IP
4.63
3.16
4.87
3.22
5.08
3.28
Indoor 27°C/19°C