Panasonic CS-W18CKP Service Manual page 21

Hide thumbs Also See for CS-W18CKP:
Table of Contents

Advertisement

Heating Operation Time Diagram
Deicing Control
Deice starts to prevent frosting at outdoor heat exchanger.
• Normal Deicing
Deice operation detection commences in Heating operation starts or 60 minutes after previous deice operation. If the
outdoor piping temperature drops to -4°C or 50 sec. continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
• Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and
after compressor starts for 1 minutes, deicing starts.
• Deicing ends when
(a) 12 minutes after deicing operation starts;
(b) The outdoor piping temperature rises to about 12°C.
• After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.
21
CS-W18CKP CU-W18CKP5 / CS-W24CKP CU-W24CKP5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu-w24ckp5Cu-w18ckp5Cs-w24ckp

Table of Contents