Attached accessories
Applicable piping kit
CZ-4F5, 7, 10AN (C18BK, A18BK, V18BK, W18BK, V18CK,
W18CK)
CZ-52F5, 7, 10AN (C24BK, A24BK, XC24BK, V24BK, W24BK,
V24CK, W24CK)
SELECT THE BEST LOCATION
INDOOR UNIT
• There should not be any heat source or steam near the
unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place
where
noise
consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
• Recommended installation height for indoor unit shall be
at least 2.3 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short
circuit of the discharged air.
• If piping length is over 7.5m, additional refrigerant
should be added as shown in the table.
prevention
is
taken into
Example: For A24BK
If the unit will be installed at a 10m distance, the quantity of
additional refrigerant should be 75g...(10 - 7.5)m × 30g/m =
75g
Indoor/Outdoor Unit Installation Diagram
• This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
37