Siemens FDOOT241-9 Technical Manual page 87

Automatic fire detectors
Hide thumbs Also See for FDOOT241-9:
Table of Contents

Advertisement

Use as
Parameter
set no.
Neural fire
2
detector
4
(FDOOT)
5
6
7
0 (ES ≥ 13)
0 (ES < 13)
8
9
Wide-spectrum
0
smoke detector
1
(FDO)
2
3
Heat detector
0 ... 4
(FDT)
Building Technologies
Fire Safety & Security Products
Collective maximum current connection factor / Alarm verification
(FDOOT241-9)
The default parameter set (parameter set 0) is set in all fire detectors when
delivered.
Parameter set name
Maximum
current
connection
factor for ES
<30
Robust
2
Balanced
Suppression
Fast Response
2
High Compensation
2
High Compensation
Insensitive
1,5
High Suppression
High Sensitive Fast
Universal
2
Universal
Robust
Sensitive
2
all parameter sets
2
For CS1115 the maximum current connection factor values in the column
1
apply for ES < 30
Different load factors due to the different measuring cycles
2
Maximum
Alarm verification on
current
control panel
connection
permitted with
factor for ES
detector ES < 13
<30
(verification time at
1
the control panel
≥ 50 s)
1,5
No
1,5
Yes
1,5
No
2
1,25
Yes
2
No
1,5
1,5
1,5
No
1,5
Yes
1,5
No
Specifications
Alarm verification on
control panel
permitted with
detector ES ≥13
(verification time at
the control panel ≥
30 s)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
87
007004_k_en_--
16.04.2009