Neural Fire Detector Fdoot221; Description; Application; Specification - Siemens FDOOT241-9 Technical Manual

Automatic fire detectors
Hide thumbs Also See for FDOOT241-9:
Table of Contents

Advertisement

Project engineering
4.3.4

Neural fire detector FDOOT221

4.3.4.1

Description

4.3.4.2

Application

No.
Name
Risk of injury to
persons
small ...
large
2
Standard
4
Standard Plus
4.3.4.3

Specification

No.
Name
Optical
Response time
[s]
2
Standard
64
4
Standard Plus
50
48
Building Technologies
Fire Safety & Security Products
Standard (2):
The priority of the 'Standard' parameter set is set to robust response. It is thus
particularly suited for us in rooms where deceptive phenomena such as cigarette
smoke or dust can be expected.
Standard Plus (4):
This parameter set is fast and highly sensitive. It is thus especially suited to rooms
without deceptive phenomena, where the priority is on early fire detection.
Concentration of
Room geometry
valuable items
low...
simple...
high
complex
Sensitivity, open
Sensitivity,
fire
smoldering fire
[%/m]
[%/m]
3,2
11,4
2,3
8
Applicable with fast temperature increases >10 K/min.
1
All parameter sets meet the criteria of standard EN 54-7.
Deceptive
Risk of fire
phenomena
few...
small ...
many
large
Thermal
Static activation
Differential activation
temperature
temperature
[°C]
∆T [K]
80
29
80
25
Critical fire size
small ...
medium
1
007004_k_en_--
16.04.2009

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fdoot221Fdoot241-8Fdo241Fdo221Fdt241Fdt221

Table of Contents