Siemens FDOOT241-9 Technical Manual page 43

Automatic fire detectors
Hide thumbs Also See for FDOOT241-9:
Table of Contents

Advertisement

Building Technologies
Fire Safety & Security Products
Sensitive (0):
This parameter set is only available with the FDOOT241-8 in MS8 operation. It has
been specially developed for the migration of ionization detectors to MS8 control
panels.
Regarding sensitivity and response time, the FDOOT2418 with the 'Sensitive'
parameter set reacts in a similar way to an MS8 ionization detector. The difference
in the response behavior of an optical and an ionization detector must be taken into
account.
When the detector is migrated to an FDnet detector line the parameter setting
should be changed to 'Fast Response'.
Fast Response (6):
This parameter set reacts in a fast and highly sensitive manner. It is thus especially
suited for rooms without deceptive phenomena, where the priority is on detecting
the fire as early as possible.
High Sensitive Fast (9):
This parameter set is suited for applications requiring very high sensitivity levels. It
reveals a significantly higher optical and thermal sensitivity than 'Fast Response'.
This parameter set is also suited for applications that can otherwise only be
covered with special detectors.
Download 1 (14) / Download 2 (15):
Application-specific parameter sets that can be loaded on site (depending on the
control panel).
Project engineering
43