Brute Deluxe
500-2000), Install & Operating
down aside the boiler. This is available as a Commercial
Kit from the manufacturer.
Part numbers for the low profile terminals to cover the
vent and combustion air openings are shown in Table 6.
SECTION 3.
Gas Supply and Piping
3.1 Gas Supply and Piping
Gas piping should be supported by suitable hangers
or floor stands, not by the appliance.
Brute Deluxe's gas train allows the user to pipe the
gas from either the right side or the left side of the unit.
As shipped, the right side of the gas train is capped off,
and there is a manual valve on the left side. If desired,
the manual valve on the left side of the gas train may
be moved to the right side, and the cap on the right side
may be moved to the left.
Review the following instructions before
proceeding with the installation.
1.
Verify that the appliance is fitted for the proper type
of gas by checking the rating plate. Brute Deluxe
appliances are equipped to operate at elevations up
to 10,000 feet (3050m). Brute Deluxe appliances
may be adjusted to operate properly at altitudes
above 2500 feet (see
will be reduced if the heating value of the gas
supply is below sea level values.
2.
The maximum inlet gas pressure must not exceed
13" W.C (3.2kPa). The minimum inlet gas pressure
is 5" W.C. (1.2kPa).
3.
Refer to
Table
7, size supply.
4.
Run gas supply line in accordance with all
applicable codes.
5.
Locate and install manual shutoff valves in
Figure 5. Typical Gas Train Configuration.
Section
6.6.2) and the input
accordance with state and local requirements.
6.
A sediment trap must be provided upstream of the
gas controls.
7.
All threaded joints should be coated with piping
compound resistant to action of liquefied petroleum
gas.
8.
The appliance and its individual shutoff valve must
be disconnected from the gas supply piping during
any pressure testing of that system at test pressures
in excess of 1/2 PSIG (3.45kpa).
9.
The unit must be isolated from the gas supply
system by closing its individual manual shutoff
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than
1/2 PSIG (3.45kpa).
10. The appliance and its gas connection must be leak
tested before placing it in operation.
11. Purge all air from gas lines.
Do not use open flame to check for leaks. An open
flame could lead to explosion, which could result in
property damage, serious injury or death.
NOTE: The Brute Deluxe appliance and all other gas
appliances sharing the gas supply line must be firing at
maximum capacity to properly measure the inlet supply
pressure. The pressure can be measured at the supply
pressure port on the gas valve. Low gas pressure could
be an indication of an undersized gas meter, undersized
gas supply lines and/or an obstructed gas supply line.
SECTION 4A.
20°F
Unit
Size
flow
H/L
flow
gpm
feet
gpm
500
43
1.7
34
750
64
3.3
51
1000
85
5.0
68
1250
106
8.1
85
1500
128
10.0
102
1750
N/R
N/R
119
2000
N/R
N/R
136
Metric Equivalent
11°C
Unit
Size
flow
H/L
flow
lpm
m
lpm
500
161
0.5
129
750
241
1.0
193
1000
321
1.5
257
1250
401
2.5
322
1500
483
3.0
386
1750
N/R
N/R
451
2000
N/R
N/R
515
Notes: gpm = gallons per minute, lpm = liters per minute,
H/L = headloss, ft = headloss in feet, m = headloss in meters.
Maximum temperature rise is 35°F (19°C), as shown. Headloss is
for boiler's heat exchanger only. N/R = not recommended.
Table 8. Water Flow Requirements — BMT2H.
Page 13
WARNING
25°F
30°F
35°F
H/L
flow
H/L
flow
feet
gpm
feet
gpm
1.1
28
0.9
24
2.3
43
1.7
36
3.6
57
3.1
49
6.1
71
4.7
61
7.2
85
5.5
73
10.5
99
8.4
85
12.5
113
10.4
97
14°C
17°C
19°C
H/L
flow
H/L
flow
m
lpm
m
lpm
0.3
107
0.3
92
0.7
161
0.5
138
1.1
214
0.9
184
1.9
269
1.4
231
2.2
322
1.7
276
3.2
375
2.6
322
3.8
429
3.2
368
H/L
feet
0.7
1.2
2.2
3.4
4.2
5.8
8.3
H/L
m
0.2
0.4
0.7
1.0
1.3
1.8
2.5

Hide quick links: