Damper equipped gas water heater

Advertisement

Quick Links

DAMPER EQUIPPED
GAS WATER HEATER
A Spanish language version of these instructions is available by contacting
the company listed on the rating plate.
La version espanola de estas instrucciones se puede obtener al escribirle
a la fabrica cuyo nombre aparece en la placa de especificaciones.
INSTALLATION & OPERATION INSTRUCTION
MANUAL For Flammable Vapor Ignition Resistant
System Equipped Water Heater
WARNING:
If the information in these instructions is not followed
exactly, a fire or explosion may result causing property damage,
personal injury or death.
For Your Safety
Do not store or use gasoline or other flammable, combustible,
or corrosive vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
For your family's comfort, safety and convenience, we recommend this
water heater to be installed and serviced by a plumbing professional.
238-47993-00A 05/09

Advertisement

Table of Contents
loading

Summary of Contents for Bradford White D4403S series

  • Page 1 DAMPER EQUIPPED GAS WATER HEATER A Spanish language version of these instructions is available by contacting the company listed on the rating plate. La version espanola de estas instrucciones se puede obtener al escribirle a la fabrica cuyo nombre aparece en la placa de especificaciones. INSTALLATION &...
  • Page 2 CONGRATULATIONS! You have just purchased one of the finest water heaters on the market today! This installation, operation and instruction manual will explain in detail the installation and maintenance of your new Damper Equipped Flammable Vapor Ignition Resistant Gas Water Heater. We strongly recommend that you contact a plumbing professional for the installation of this water heater.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS Page SPECIFICATIONS..............4 GENERAL INFORMATION .............5 INSTALLATION...............7 Locating the Water Heater ..........7 Minimum Clearances ............10 Venting................11 Combustion Air Supply ..........12 Water Connections ............14 Gas Connections ............17 Electrical Connections ..........18 Wiring Diagram .............19 GENERAL OPERATION ............20 Lighting and Shutdown Instructions ......21 Thermostat Adjustments..........22 Burner Flame Check .............23 MAINTENANCE ..............24...
  • Page 4: Specifications

    SPECIFICATIONS Figure 1 Approx. Dimensions (in.) Capacity Input (gal.) (Btu/hr) D4403S*F 38,000 55 1/2 41 1/2 11 1/2 49 1/2 (BN,SX) D4504S*F 40,000 11 ½ 56 ½ (BN,SX) * denotes warranty year BN denotes natural gas SX denotes LP...
  • Page 5: General Information

    GENERAL INFORMATION This gas-fired water heater is design certified by CSA International under the applicable American National Standard, Z21.10.1-Latest Edition or CSA 4.1- Latest Edition, available from CSA International, 8501 East Pleasant Valley Road, Cleveland, OH 44131-5575, USA. This water heater must be installed in accordance with local codes. In the absence of local codes, it must be installed in compliance with the National Fuel Gas Code, ANSI Z223.1-Latest Edition, or in Canada, Natural Gas Installation Code, CAN/CGA B149.1-Latest Edition, or Propane Installation...
  • Page 6 General Information continued- IMPORTANT Before proceeding, please inspect the water heater and components for possible damage. DO NOT install any damaged components. If damage is evident, please contact the supplier where the water heater was purchased or the manufacturer listed on the rating plate for replacement parts. This water heater has been manufactured for operation at altitudes from sea level to 2000 feet (610 m) (unless otherwise specified on the water heater rating plate).
  • Page 7: Installation

    INSTALLATION Locating the Water Heater WARNING Water heaters are heat producing appliances. To avoid damage or injury, there shall be no materials stored against the water heater or vent-air intake system, and proper care shall be taken to avoid unnecessary contact, especially by children, with the water heater and vent-air intake components.
  • Page 8 Installation (Locating the Water Heater) continued- Note: For California installations, this water heater must be braced, anchored, or strapped to avoid falling or moving during an earthquake. See instructions for correct installation procedures. Instructions may be obtained from DSA Headquarters Office, 1102 Q Street, Suite 5100, Sacramento, California 95811.
  • Page 9 Installation (Locating the Water Heater) continued- WARNING DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE NOT CERTAIN OF THE FOLLOWING: • Liquefied petroleum gases/propane gas and natural gas have an odorant added by the gas supplier that aids in detection of the gas. •...
  • Page 10: Minimum Clearances

    Minimum Clearances WARNING Failure to adhere to these installation and operating instructions may create a hazard to life and property and will nullify the warranty. This installation shall allow access to the front of the water heater and adequate clearance shall be provided for servicing and operating this water heater.
  • Page 11: Venting

    Venting WARNING The venting system must be installed properly following all local codes or in the absence of local codes, the National Fuel Gas Code, ANSI Z223.1-Latest Edition, or in Canada, The Natural Gas and Propane Installation Code, B149- Latest Edition. Failure to properly install the venting system could result in property damage, personal injury, or death.
  • Page 12: Combustion Air Supply

    Venting continued- This water heater must be connected to a lined masonry chimney or venting system approved by local codes or ordinances. The vent connector used to attach the draft hood outlet to the chimney or approved vent must be of the same diameter as the draft hood outlet or larger.
  • Page 13 Combustion Air Supply continued- Confined Spaces Confined spaces are spaces defined as having less than 50 ft of space per 1,000 BTU (1.41 m /.29 kw) per hour of input. Unconfined Spaces In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation, and dilution of flue gases.
  • Page 14: Water Connections

    Water Connections Note: BEFORE PROCEEDING WITH THE INSTALLATION, CLOSE THE MAIN WATER SUPPLY VALVE. After shutting off the main water supply, open a faucet to relieve the water line pressure to prevent any water from leaking out of the pipes while making the water connections to the water heater.
  • Page 15 Installation (Water Connections) continued- WARNING For protection against excessive temperatures and pressure, install temperature and pressure protective equipment required by local codes, but not less than a combination temperature and pressure relief valve certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials as meeting the requirements of the Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22 or the Standard...
  • Page 16 Installation (Water Connections) continued- WARNING Hydrogen gas can be produced in an operating water heater that has not had water drawn from the tank for a long period of time (generally two weeks or more). Hydrogen gas is extremely flammable. To prevent the possibility of injury under these conditions, we recommend the hot water faucet to be open for several minutes at the kitchen sink before you use any electrical appliance, which is connected to the hot water system.
  • Page 17: Gas Connections

    Gas Connections The gas supply lines must meet all requirements of the National Fuel Gas Code, ANSI Z223.1-Latest Edition, or in Canada, the Natural Gas Installation Code, CAN/CGA B149.1-Latest Edition, or Propane Installation Code, CAN/CGA B149.2-Latest Edition. The minimum permissible gas supply pressure for the purpose of input adjustment is 1 in.
  • Page 18: Electrical Connections

    Gas Connections continued- CAUTION The water heater and an individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 1/2 psi (3.5 kPa). The water heater must be isolated from the gas supply piping system by closing its manual shut-off valve during any pressure testing of the gas supply system at test pressures equal to or less than 1/2 psi (3.5 kPa).
  • Page 19: Wiring Diagram

    Wiring Diagram FLEXIBL DAMPE LINE (MOUNTED ON OF WATER BUSHIN DAMPE HOUSIN PILO DAMPE MOTO DAMPE Honeywell CIRCUIT BOAR VERY WATE TEMPERATURE SENSO FLAMMABL VAPOR RESETTABL THERMAL SWITCH 115 VOLTS 60HZ SINGLE PHASE POWER SUPPLY CONTROL DAMPE DAMPE CIRCUIT IGNITE BOAR WATER TEMPERATURE SENSO...
  • Page 20: General Operation

    GENERAL OPERATION WARNING Water heaters are heat producing appliances. To avoid damage or injury, there shall be no materials stored against the water heater or vent-air intake system, and proper care shall be taken to avoid unnecessary contact (especially by children) with the water heater and vent-air intake system. UNDER NO CIRCUMSTANCES SHALL FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT THINNER BE USED OR STORED IN THE VICINITY OF THIS WATER HEATER, VENT-AIR INTAKE SYSTEM OR IN...
  • Page 21: Lighting And Shutdown Instructions

    Lighting and Shutdown Instructions WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. STATU Honeywel VERY...
  • Page 22: Thermostat Adjustments

    Thermostat Adjustments The thermostat dial is adjusted to its lowest setting when shipped from the factory. When adjusting the thermostat, it should be remembered that lower temperature settings are more energy efficient. To adjust the thermostat, turn the dial clockwise until the minimum acceptable temperature is set. It is suggested that the starting point setting not exceed the 120°F (49°C) or “HOT”...
  • Page 23: Burner Flame Check

    General Operation continued- DANGER Hotter water increases the risk of scald injury. Scalding may occur within five ° (5) seconds at a temperature setting of 140°F (60 C). To protect against hot water injury, install an ASSE approved mixing valve in the water system. This valve will reduce point of discharge temperature by mixing cold and hot water in branch water lines.
  • Page 24: Maintenance

    MAINTENANCE WARNING Water heaters are heat producing appliances. To avoid damage or injury, there shall be no materials stored against the water heater or vent-air intake system, and proper care shall be taken to avoid unnecessary contact (especially by children) with the water heater and vent-air intake system. UNDER NO CIRCUMSTANCES SHALL FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT THINNER BE USED OR STORED IN THE VICINITY OF THIS WATER HEATER, VENT-AIR INTAKE SYSTEM OR IN...
  • Page 25 Maintenance continued- 5. Annually remove the inner door and main burner assembly to clean orifices and related parts of any dirt or other foreign material. Inspect the burner ports for obstructions or debris and clean with a wire brush as needed.
  • Page 26 Maintenance continued- 6. At least once a year, check the combination temperature and pressure relief valve to ensure that the valve has not become encrusted with lime. Lift the lever several times until the valve seats properly without leaking and operates freely. 7.
  • Page 27 Maintenance continued- CAUTION FOR YOUR SAFETY, DO NOT ATTEMPT REPAIR OF COMBINATION GAS CONTROL, BURNERS, OR GAS PIPING. REFER REPAIRS TO A QUALIFIED SERVICE TECHNICIAN. Contact your supplier or plumbing professional for replacement parts or contact the company at the address given on the rating plate of the water heater.
  • Page 28: Troubleshooting

    TROUBLESHOOTING LED Status Control Status Probable Cause None (LED not on Electrical pow er not Control pow er sw itch in " OFF" position. or flashing) present Supply voltage interrupted. One short flash Stand-by mode, Temperature demand is satisfied (no call for every four Thermostat is satisfied (no heat)
  • Page 29 Troubleshooting continued- LED Status Control Status Probable Cause 1. Damper not in proper position or Damper test circuit not Six flashes, tw o malfunctioning - damper moved from full w orking properly during flashes, three open position during run cycle burner operation, system second pause 2.
  • Page 30 Troubleshooting continued- Control Sequence of Operation Start up Sequence Upon powering up, the control checks for the presence of the flammable vapor sensor, if the resistance is in the expected range the control will begin normal operation after 5 to 8 seconds. Normal Heating Sequence 1.
  • Page 31: Installation For Potable Water

    INSTALLATION FOR POTABLE WATER Figure 5...
  • Page 32: Parts List Drawing

    PARTS LIST DRAWING Figure 6...
  • Page 33: Parts List

    PARTS LIST PART NAME AND DESCRIPTION 1. Draft Hood 15. Inner Door Assembly (Right) 2. Damper 15A. High Temperature Limit Switch 3. Jacket Head Pan 16. Inner Door (Left) 4. Jacket 17. Damper Wire Harness 5. Heat Trap—Cold Water Inlet 18.
  • Page 34: Installation Instructions For Potable Water And Space Heating

    Installation Instructions for Potable Water and Space Heating 1. All piping components connected to this water heater for space heating applications must be suitable for use with potable water. In Massachusetts, space heating piping length must not exceed 50 feet (15.2 m).
  • Page 35: Notes

    NOTES...
  • Page 36 NOTES...