Operate the [c]FP-RTD-122 only at or below Pollution
Degree 2. Pollution Degree 2 means that only nonconductive
pollution occurs in most cases. Occasionally, however, a
temporary conductivity caused by condensation must be
expected.
Refer to the FieldPoint product label for regulatory
certification under hazardous location standards. If the
FieldPoint product is not certified for operation in hazardous
locations, do not operate it in an explosive atmosphere or
where there may be flammable gases or fumes.

Specifications

These specifications are typical for the range –40 to 70°C unless
otherwise noted. Gain error is calculated as a percentage of input
signal value.
Input Characteristics
Number of channels.......................... 8
ADC resolution................................. 16 bits
Type of ADC..................................... Delta-sigma
Input signal ranges (software selectable by channel)
Temperature................................ 73 to 1123 K
Resistance................................... 0 to 400
Temperature accuracy (includes 5% matched,
0.5
lead wires—10 m of 22 AWG copper)
Measured Value
–200 to 150 °C
150 to 850 °C
Resolution ......................................... 0.016 °C
Resistance accuracy
Offset error, 400
15 to 35 °C ........................... 0.03
–40 to 70 °C......................... 0.08
© National Instruments Corp.
15 to 35 °C
Typical
Maximum
0.15
0.30
0.25
0.50
range
11
–200 to 850 °C
–328 to 1562 °F
or 0 to 4,000
Error
–40 to 70 °C
Typical
0.40
0.90
typ, 0.08
typ, 0.4
FP-RTD-122 and cFP-RTD-122
Maximum
1.6
3.0
max
max