The owner should inspect the system monthly for damage, water stains, signs of rust, corrosion, and exhaust vent and air intake
blockage. If inspection of the unit shows signs of damage, the appliance should be shut off until the problem is repaired by a qualified
technician.
After installation, all appliance safety devices should be tested.
This appliance is certified for indoor installations only. The appliance consists of gas ignition system components which must be
protected from water (dripping, spraying, etc.) during operation and service. Carefully consider installation location and the placement of
critical components (circulators, condensate neutralizers, etc.) before installing the appliance.
DO NOT allow children to operate this unit. DO NOT use this unit if it does not appear to be operating correctly. A qualified technician
should service and inspect the appliance annually.
The appliance DHW temperature is factory set to 125
before bathing, showering, washing, etc. DO NOT adjust the water temperature while the appliance is being used by other persons.
If the appliance is exposed to the following, do not operate until all corrective steps have been made by a qualified service technician:
1. FIRE
2. DAMAGE
3. WATER
This appliance is equipped with a three prong plug. It should only be plugged directly into a properly grounded three prong receptacle.
DO NOT remove the ground plug from the plug.
DO NOT alter or modify the appliance or appliance controls. This can be dangerous and WILL VOID the warranty.
Failure to follow these statements could result in property damage, severe personal injury, or death.
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
This appliance provides a overheat shutdown limit. In the event the appliance water exceeds the set point of the control limit, the cutoff
will trip and the appliance will shut down. Certain local codes require additional temperature limits. In addition, certain types of systems
may operate at temperatures below the minimum set point of the limit provided with the appliance. Contact a qualified service
technician for additional overheat controls.
NOTE: When inquiring about service or troubleshooting, reference the model and serial numbers from the appliance rating label.
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN SUBMERGED IN WATER. Immediately call a qualified service technician.
The appliance MUST BE replaced if it has been submerged. Attempting to operate an appliance that has been submerged could create
numerous harmful conditions, such as a potential gas leakage causing a fire and/or explosion, or the release of mold, bacteria, or other
harmful particulates into the air. Operating a previously submerged appliance could result in property damage, severe personal injury,
or death.
NOTE: Appliance damage due to flood or submersion is considered an Act of God, and IS NOT covered under product warranty.
Be sure to disconnect electrical power before opening appliance cabinet or performing service. Label all wires while performing service
to ensure proper re-wiring of the appliance. Wiring errors can cause improper or dangerous operation. Failure to do so could result in
an electrical shock, improper appliance operation, property damage, serious personal injury, or death.
Due to the low water content of the appliance, improper sizing of the appliance with regard to heating system load will result in
excessive cycling and accelerated component failure. Westinghouse DOES NOT warrant failures caused by improperly sized appliance
applications. DO NOT oversize the appliance to the system. Modular appliance installations greatly reduce the likelihood of appliance
oversizing.
B. IMPROPER COMBUSTION
Do not obstruct the flow of combustion and ventilating air. Adequate air must be provided for safe operation. Failure to keep the
exhaust vent and intake pipe clear of ice, snow, or other debris could result in property damage, serious personal injury, or death.
C. GAS
Should overheating or gas supply fail to shut off, do not turn off or disconnect electrical supply to the circulator. Instead, shut off the gas
supply at a location external to the appliance.
o
o
F (51
C). To avoid scalding, always check the temperature of the hot water
NOTICE
9
WHL-015 REV. 5.20.16

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wbrc**199f

Table of Contents