COMBUSTION ADJUSTMENT

In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment
and testing must be carried out observing the instruction manual of the boiler, including verification of
the CO and CO
concentration in the flue gases, their temperatures and the average temperature of
2
the water in the boiler.
To suit the required appliance output, fit the nozzle then adjust the pump pressure, the setting of the
combustion head and the air damper opening in accordance with the following schedule.
LIGHT OIL FUEL
1
Nozzle
GPH
Angle
0.60
60° / 80°
0.65
60° / 80°
0.75
60°
0.85
60°
1.00
60°
1.10
60°
1.10
60°
KEROSENE FUEL
1
Nozzle
GPH
Angle
0.75
60°
0.85
60°
1.00
60°
1.10
60°
1.25
60°
1.35
60°
1.50
60°
1.50
60°
1
NOZZLES RECOMMENDED: Monarch type R - NS ; Delavan type W -A - E
Angle: 60° - in most cases.
80° - in case of flame detachment, during ignitions at low temperatures.
2
PRESSURE:
8 bar: the pump leaves the factory set at this value, which is suitable only for kerosene.
10 bar: maximum pressure for kerosene.
FOR LIGHT OIL INCREASE PRESSURE
12 bar: in most cases.
14 bar: improves flame retention; it is therefore suitable for ignitions at low temperatures.
2381
2
Pump pressure
Burner output
bar
12
12
12
12
12
12
13
2
Pump pressure
Burner output
bar
8
8
8
8
8
8
8
10
Steinen type Q - H
Comb. head
adjustment
kg/h ± 4%
Set-point
2.6
2.8
3.2
3.7
4.3
4.8
5.0
Comb. head
adjustment
kg/h ± 4%
Set-point
2.2
2.5
2.9
3.2
3.7
4.0
4.4
5.0
; Danfoss type B - H
5
3
4
Air damper
adjustment
Set-point
1.5
2
2
2.2
2.5
2.5
3
3
4
4.5
5
6
6
7
3
4
Air damper
adjustment
Set-point
1
2
1.5
2
2
2.3
2.5
2.5
3
3
4
4
5
5
6
7