Riello G5 444T50 Operation Manual

Riello G5 444T50 Operation Manual

Light oil - kerosene burners

Advertisement

Installation, use and maintenance instructions
Light oil - kerosene burners
One stage operation
CODE
3744451
3744452
MODEL
G5
G5
TYPE
444T50
444T50
2902381 (2)

Advertisement

Table of Contents
loading

Summary of Contents for Riello G5 444T50

  • Page 1 Installation, use and maintenance instructions Light oil - kerosene burners One stage operation CODE MODEL TYPE 3744451 444T50 3744452 444T50 2902381 (2)
  • Page 3: Technical Data

    TECHNICAL DATA Thermal power – output 28 – 60 kW – 2.3 – 5 kg/h Light oil 35s, max. viscosity at 20 °C: 6 mm Fuel Kerosene 28s ± 10% Electrical supply Single phase, 230 V 50Hz Motor Run current 0.85 A – 2850 rpm – 298 rad/s 4 µF Capacitor Ignition transformer...
  • Page 4: Firing Rate

    FIRING RATE, (as EN 267) Fuel output - kg/h Thermal power - kW D5226 OVERALL DIMENSIONS Flange Burner D5554 MOUNTING THE BURNER BURNER FIXING AND It is necessary that the insulating gasket HINGE ASSEMBLY (9, fig. 1) is placed between the boiler door and the burner flange.
  • Page 5: Oil Lines

    OIL LINES PRIMING THE PUMP L meters Loosen the plug of the vacuum I. D. I.D. gauge (5, fig. 1) and wait until the meters 8 mm 10 mm fuel flows out. D5219 H = Difference of level. D5199 L = Max. length of the L meters suction line.
  • Page 6: Electrical Wiring

    ELECTRICAL WIRING 230V 50Hz WARNING Do not exchange the neutral with the phase. Switch with fuse 6A max. Regulating thermostat Limit thermostat with manual resetting Remote lock-out lamp (230V - 0.5A max.), if required Terminal block of control-box 530SE Valve Black Capacitor Motor...
  • Page 7: Combustion Adjustment

    COMBUSTION ADJUSTMENT In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment and testing must be carried out observing the instruction manual of the boiler, including verification of the CO and CO concentration in the flue gases, their temperatures and the average temperature of the water in the boiler.
  • Page 8: Combustion Head Setting

    COMBUSTION HEAD SETTING This is done when fitting the nozzle, with the blast tube removed. It depends on the output of the burner and is carried out by rotating the regulating rod, till the terminal plane of the blast tube is level with the set-point, as indicated in the schedule.
  • Page 9: Air Damper Adjustment

    AIR DAMPER ADJUSTMENT : The mobile air damper (1) operated by the jack (2) assures the complete opening of the air intake. The regulation of the air-rate is made by adjusting the fixed air damper (3), after loosing the screws (4). When the optimal regulation is reached, screw tight the screws (4) to assure a free movement of the mobile air damper (1).
  • Page 10: Burner Start-Up Cycle

    BURNER START-UP CYCLE Normal Lock-out, due to light-failure Thermostat Motor Ignition transformer Valve Flame Lock-out lamp D5229 ONLY FOR LIGHT OIL ADJUSTMENTS, TO AVOID FLAME - DETACHMENT, AT BURNER - IGNITION This inconvenience can occur, when the temperature of the light oil decreases below +8 °C. CORRECT POSITIONING OF THE ELECTRODES IMPORTANT: THESE DIMENSIONS...
  • Page 11: Safety Warnings

    SAFETY WARNINGS The dimension of the boiler’s combustion chamber must respond to specific values, in order to guarantee a combustion with the lowest polluting emissions rate. The Technical Service Personnel will be glad to give you all the imformation for a correct match- ing of this burner to the boiler.