Combustion Air Supply continued-
Confined Spaces
Confined spaces are spaces defined as having less than 50 ft
1,000 BTU (1.41 m
Unconfined Spaces
In unconfined spaces in buildings, infiltration may be adequate to provide air
for combustion, ventilation, and dilution of flue gases. However, in buildings of
tight construction (for example, weather stripping, heavily insulated, caulked,
vapor barrier, etc.), additional air may need to be provided using the methods
described below.
All Air from Inside the Building: The confined space must be provided with
two permanent openings communicating directly with an additional room(s) of
sufficient volume, so that the combined volume of all spaces meets the criteria
for an unconfined space. The total input of all gas utilization equipment
installed in the combined space must be considered in making this
determination. Each opening must have a minimum free area of 1 square
inch per 1,000 BTU (6.45 cm
gas utilization equipment in the confined space, but not less than 100 square
inches (645 cm
one within 12 in. (31 cm) of the bottom of the enclosure.
All Air from Outdoors: The confined space must be provided with two
permanent openings, one commencing within 12 in. (31 cm) of the top and
one commencing within 12 in. (31 cm) from the bottom of the enclosure. The
openings must communicate directly, or by ducts, with the outdoors or spaces
(crawl or attic) that freely communicate with the outdoors.
1. When directly communicating with the outdoors, each opening must have
a minimum free area of 1 square inch per 4,000 BTU (6.45 cm
per hour of total input rating of all equipment in the enclosure.
2. When communicating with the outdoors through vertical ducts, each
opening must have a minimum free area of 1 square inch per 4,000 BTU
2
(6.45 cm
/1.2 kw) per hour of total input rating of all equipment in the
enclosure.
3. When communicating with the outdoors through horizontal ducts, each
opening must have a minimum free area of 1 square inch per 2,000 BTU
2
(6.45 cm
/.6 kw) per hour of total input rating of all equipment in the
enclosure.
4. When ducts are used, they must be of the same cross-sectional area as
the free area of the openings to which they connect. The minimum
dimension of rectangular air ducts must be not less than 3 in. (7.5 cm).
Specially Engineered Installations
The requirements noted under CONFINED SPACES above shall not
necessarily govern when special engineering, approved by the authority
having jurisdiction, provides an adequate supply of air for combustion,
ventilation, and dilution of flue gases.
3
/.29 kw) per hour of input.
2
/.29 kw) per hour of the total input rating of all
2
). One opening must be within 12 in. (31 cm) of the top and
12
3
of space per
2
/1.2 kw)