Mitsubishi Electric MXZ-2D33VA Service Manual page 136

Hide thumbs Also See for MXZ-2D33VA:
Table of Contents

Advertisement

Indication
No.
Symptom
LED1(Red) LED2(Yellow)
21 'Outdoor unit
13 times
Not lighted
stops and
restarts
22
Lighted
3 minutes
later' is
23
repeated.
Lighted
24
Lighted
25 Outdoor unit
Once
operates.
26
Twice
27
3 times
28
4 times
29
5 times
30
7 times
31 Outdoor
unit
operates
normally.
7 times
32
33
8 times
34
Lighted
NOTE 1. The location of LED is illustrated at the right figure. Refer to 11-7.2.
2. LED is lighted during normal operation.
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is "2".
ON
2.5-second OFF
OFF
OBH626K
Abnormal point / Con-
dition
Outdoor fan motor
Current sensor protec-
8 times
tion
Communication
11 times
between P.C. boards
protection
Zero cross detecting
12 times
circuit (outdoor power
P.C. board)
Primary current protec-
Lighted
tion
High-pressure protec-
tion
Lighted
Defrosting in cooling
Discharge temperature
Lighted
protection
Low discharge
Lighted
temperature protection
Cooling high-pressure
Lighted
protection
High
Low
Pressure bypass
valve
Lighted
Cooling evaporating
temperature drop
prevention control
High
Low
pressure bypass valve
High pressure protec-
tion control at start-up
of heating operation
Lighted
High
Low
pressure bypass valve
Compressor oil temper-
ing control at start-up of
heating operation
Cooling evaporating
Lighted
temperature
protection
Lighted
Normal
0.5-second ON
2.5-second OFF
Condition
A failure occurs 3 consecutive times within 30
seconds after the fan gets started.
A short or open circuit is detected in the current
sensor during compressor operating.
Communication error occurs between the outdoor
control P.C. board and outdoor power P.C. board
for more than 10 seconds.
Zero cross signal cannot be detected while the
compressor is operating.
The input current exceeds 15 A.
The indoor gas pipe temperature exceeds 45°C
during heating.
The indoor gas pipe temperature falls 3°C or below
during cooling.
The frequency of the compressor is kept 80 Hz or
more and the discharge temperature is kept under
50°C(COOL mode)/40°C(HEAT mode) for more
than 40 minutes.
The frequency of the compressor is kept 80 Hz or
more and the discharge temperature is kept under
39°C for more than 20 minutes.
The outdoor heat exchanger temperature exceeds
58°C during operation.
During cooling operation, the temperature of indoor
heat exchanger becomes 3°C or less within 1 hour
after the compressor starts running, or it becomes
less than 12°C - 16°C* later than that.
* It depends on the difference between the set
temperature and the room temperature.
The room temperature is 24°C or more when 1 or
2 unit(s) start(s) the heating operation.
Both the following are true:
• The outside temperature is -2°C or less when the
heating operation is started.
• [(Discharge temperature) - (Indoor heat exchang-
er temperature)] < 5°C
During cooling operation, the temperature of
indoor heat exchanger becomes 7°C - 11°C*
or less within 1 hour after the compressor
starts running, or it becomes 9°C - 17°C* or
less later than that.
* It depends on the indoor unit type/model or the
difference between the set temperature and the
room temperature.
0.5-second ON
136
Remedy
• Refer to 11-6.
"Check of outdoor fan motor".
• Replace the outdoor power P.C. board.
• Check the connecting wire between outdoor con-
trol P.C. board and outdoor power P.C. board.
• Replace the outdoor power P.C. board.
These symptoms do not mean any abnormality of
the product, but check the following points.
• Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short
cycled.
• Check refrigerant circuit and refrigerant amount.
• Refer to 11-6.
"Check of LEV".
• Refer to 11-6.
"Check of outdoor thermistors".
• Refer to 11-6.
"Check of LEV".
• Check refrigerant circuit and refrigerant amount.
This symptom does not mean any abnormality of
the product, but check the following points.
• Check if indoor fi lters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short
cycled.
This symptom does not mean any abnormality of
the product, but check the following points.
• Check the indoor fi lters are not clogged.
• Check there is suffi cient refrigerant.
• Check the indoor/outdoor unit air circulation is not
short cycled.
This symptom does not mean any abnormality of
the product.
Outdoor control P.C. board
(Parts side)
LED1 LED2
Lighted