Mitsubishi Electric MXZ-2D33VA Service Manual page 123

Hide thumbs Also See for MXZ-2D33VA:
Table of Contents

Advertisement

10-6. CHANGING THE AMPERE LIMIT
With this function, you can change the current that flows in the outdoor unit.
NOTE: Use this function only when the amount of current exceeds the allowed value.
[How to change the ampere limit]
MXZ-4D83VA/5D102VA
(1) Turn OFF the power supply and make sure that the LED goes off.
(2) Set SW2 as shown in the table below.
(3) Turn ON the power supply.
SW2 on the outdoor control P.C. board
SW2
MXZ-6D122VA
(1) Be sure to turn off the main power for the air conditioner before making the setting.
(2) Make the setting referring to the table below.
(3) Turn ON the power supply.
SW2 on the outdoor control P.C. board
SW2
OBH626K
MXZ-4D83VA/5D102VA
10.5 A
15.5 A
Default setting
Full
MXZ-6D122VA
20 A
Default setting
Full