6.7.8 Calculation of compensation factor

i
NOTICE
!
WARNING
42
The compensation factor eliminates or reduces the natural effect of derate of maximum
input caused by the resistance of the vent system and/or the impact of the altitude.
1. Determine the Compensation Factor Vent System CF(V) in the table below.
Eq. length (ft)
min
max
0
10
11
20
21
30
31
40
41
60
61
80
81
100
Compensation factor vent system CP(V)
2. Determine the Compensation Factor Altitude CF(A) in the table below.
Altitude (ft)
min
max
0
1
1,000
2,000
2,000
3,000
3,000
4,000
4,000
5,000
5,000
6,000
6,000
7,000
7,000
8,000
8,000
9,000
9,000
10,000
Compensation factor altitude CP(A)
Any application or installation above 10,000 must be reviewed by Rinnai's
Engineering group. This is to ensure the product is installed and the overall
system is designed properly and that the units are commisioned properly.
Not involving of Rinnai's Engineering group would result in no support of the
product and no warranty.
3. Calculate the Compensation Factor Total CF(T):
CF(T) = CF(V) + CF(A)
The result is the setting for Parameter 73.
Change parameter 73 according to this result. See Chapter 11.1 how to change
parameters.
Example of calculation:
QP130N
Eq. lenth vent system (taken from previous example)
Altitude
Parameter setting (Par. 73) = 48
Do not overcompensate the boiler by setting a higher value than calculated,
otherwise the boiler could be damaged.
Boiler type
QP85N
QP130N
CF (V)
0
0
0
0
0
2
1
4
2
6
3
8
4
10
Boiler type
QP85N
QP130N
CF (A)
0
6
12
18
24
30
36
42
48
54
table 10
table 11
46 ft
CF(V) = 6
7,200ft
CF(A) = 42 +
CF(T) = 48