Panasonic S-12MU1U6 Installation Instructions Manual page 65

Vrf system
Hide thumbs Also See for S-12MU1U6:
Table of Contents

Advertisement

CAUTION
(1) When linking outdoor units in a network, disconnect the terminal extended from the short plug (CN003, 2P
Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the
outdoor units. (When shipping: In shorted condition.)
For a system without link (no connection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 4-1)
Outdoor unit
Indoor unit
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes misaddress
setting. (Fig. 4-2)
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches less than 3.3 ft. are not included in the total branch number.) (Fig. 4-3)
Branch
point
16 or fewer
VRF_Indoor_US.indb 65
VRF_Indoor_US.indb 65
Outdoor unit
Indoor unit
Indoor unit
Fig. 4-1
Indoor unit
Outdoor unit
NO
Indoor unit
Fig. 4-2
Outdoor unit
Indoor unit
Indoor unit
more than 3.3 ft.
Indoor unit
Indoor unit
more than 3.3 ft.
Indoor unit
less than 3.3 ft.
Indoor unit
Fig. 4-3
Outdoor unit
Prohibited
Indoor unit
Indoor unit
Indoor unit
Branch point
Outdoor unit
Indoor unit
Indoor unit
65
Prohibited
Indoor unit
Outdoor unit
Indoor unit
Indoor unit
2011/09/30 12:23:12
2011/09/30 12:23:12