3-6-5. Checking After Installation
Check that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling
surface. Gaps may cause water leakage and condensation.
Check that the wiring is securely connected.
If it is not securely connected, the auto fl ap will not operate. ("P09" is displayed on the remote controller.) In addition,
water leakage and condensation may occur.
3-6-6. When Removing the Ceiling Panel for Servicing
When removing the ceiling panel for servicing, remove the air-intake grille and air fi lter, disconnect the wiring connector
inside the electrical component box, and then remove the 4 mounting screws.
3-6-7. Adjusting the Auto Flap
The air-direction louver on the ceiling panel outlet can be adjusted as follows.
Adjust the louver to the desired angle using the remote controller. The louver also has an automatic air-sweeping
mechanism.
NOTE
Never attempt to move the louver by hand.
Proper air fl ow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or
heating seems inadequate, try changing the direction of the air fl ow.
3-7. Special Remarks
DC Fan Tap Change Procedure
Be sure to turn OFF the power (at mains) before beginning the work below.
(1) In the table below, check the fi eld-supply parts that will be used. (If this setting is not made, the airfl ow may
decrease and condensation may occur.)
(2) Setting (a)
Open the cover of the electrical component box. Short
the short-circuit pin TP3 (2P, yellow) on the indoor unit
control PCB. (Fig. 3-28)
(3) Setting (b)
Open the cover of the electrical component box. Short
the short-circuit pin TP6 (2P, white) on the indoor unit
control PCB. (Fig. 3-28)
VRF_Indoor_US.indb 16
VRF_Indoor_US.indb 16
Setting
Air shield material (for use with 3-direction discharge)*
(a)
Air shield material (for use when a discharge duct is connected)*
(b)
Air shield material (for use with 2-direction discharge)*
Setting (a): Go to (2).
Setting (b): Go to (3).
Indoor unit control PCB
* PCB model No.: CR-SXRP56B-B
16
* Use fi eld-supply air shield material.
Fig. 3-28
2011/09/30 12:22:58
2011/09/30 12:22:58