Unit Installation

NetVanta 5305 (DC)

The DC-powered NetVanta 5305 connects to a centralized DC power source via the four-position power
connector on the rear of the chassis. The nominal input of the NetVanta 5305 is -48 VDC. Power and ground
connections require copper conductors and a ring lug.
Instructions for Connecting DC Power Source to the NetVanta 5305
Step
1
With the power disconnected, connect the primary power source to input A of the power
connector.
2
Connect a ground wire (minimum 12 AWG) to the grounding point using the screw provided.
Connect the other end of the ground wire to a protective earth ground.
3
If using a backup power source, connect it to input B of the power connector.
The ground wire shall be fitted with a number 8 ring terminal and should be fastened to the
grounding lug on the back panel of the unit. The ring terminal shall be installed using
AMP P/N 59250 T-EAD crimping tool or equivalent.
Power to the NetVanta 5305 DC system must be from a reliably grounded 48 VDC
SELV source.
Use only copper conductors (minimum 14 AWG) when making power connections.
Install unit in accordance with the requirements of NEC NFPA 70.
The branch circuit overcurrent protection shall be a fuse or circuit breaker rated
minimum 48 VDC, maximum 15 A.
A readily accessible disconnect device, that is suitably approved and rated, shall be
incorporated in the field wiring.
Maximum recommended ambient operating temperature is 50
30
NetVanta 5305 Hardware Installation Guide