Prepare boiler

Model 501

1. Remove the top access cover from the unit (no tools
required for removal).
2. Turn the adjustment screw on the gas valve clockwise until
it stops. Th en turn the adjustment screw counterclockwise
four and three quarter (4 3/4) turns (see FIG. 2-3).
3. Use a combustion analyzer to verify CO
of 9.6 – 10.5%. If not, adjust the screw counterclockwise
incrementally to raise CO
(FIG. 2-3).
4. Aft er adjustment is complete, attach the propane conversion
label (in the conversion kit bag) next to the boiler rating
plate. Attach the LP caution label (in the conversion kit bag)
to the left side of the unit in the lower left corner.
5. Replace the top access cover.
Aft er converting to LP, check combustion
WARNING
per the Start-up procedure in Section 10
of this manual. Failure to check and verify
combustion could result in severe personal
injury, death, or substantial property
damage.
Figure 2-3 Gas Valve Adjustment - Model 501

Models 601 - 801

1. Remove the top access cover from the unit (no tools
required for removal).
2. Remove the cover on top of the gas valve (FIG. 2-4).
3. Turn the adjustment screw on top of the gas valve clockwise
one and three quarter (1 3/4) turns on the 601 Model, one
and a half (1 1/2) turns on the 701 Model, and one turn on
the 801 Model (see FIG. 2-4).
4. Use a combustion analyzer to verify CO
of 9.6 – 10.5%. If not, adjust the screw counterclockwise
incrementally to raise CO
(FIG. 2-4).
5. Aft er adjustment is complete, attach the propane conversion
label (in the conversion kit bag) next to the boiler rating
plate. Attach the LP caution label (in the conversion kit
bag) to the left side of the unit in the lower left corner.
6. Replace the gas valve cover along with the top access cover.
14
is within the range
2
and clockwise to lower CO
2
ALLEN WRENCH
ADJUSTMENT SCREW
is within the range
2
and clockwise to lower CO
2
Installation & Operation Manual
Aft er converting to LP, check combustion
WARNING
per the Start-up procedure in Section
10 of this manual. Failure to check and
verify combustion could result in severe
personal injury, death, or substantial
property damage.
Figure 2-4 Gas Valve Adjustment - Models 601 - 801
COVER
2
ALLEN WRENCH

Leveling the boiler

1.
Set the boiler in place and check level.
a) Adjust legs if necessary to level boiler, see FIG. 2-5
below.
Figure 2-5 Leveling Legs on the Boiler
RAISE
2
ADJUSTMENT SCREW
SCREWDRIVER
SLOT
LOWER