Set-Up; General Information; Condensed Water Pipe; Installation - Dimplex LA 26HS Installation And Operating Instructions Manual

Advertisement

Available languages

Available languages

5

Set-up

5.1 General Information

The device should always be installed on a permanently smooth,
even and horizontal surface. The frame should lie tight on the
floor all the way round to guarantee sufficient sound insulation
and to prevent water-carrying parts from cooling down.If this is
not the case, additional insulation measures may be necessary.
If this is not the case, additional insulation measures may be nec-
essary. Natural ground, e.g., lawn should be below the air intake
and air outlet vents.If the installation conditions differ (installation
on a platform or flat roof) or there is a greater risk of the heat
pump tipping over (due to an exposed position or high wind ex-
posure), additional protection against tipping over must be pro-
vided. The responsibility for the heat pump installation lies with
the specialist system construction company. During the installa-
tion, local requirements such as building regulations, static load
of the building, and wind exposure must be accounted for.
It must be possible to carry out maintenance work without hin-
drance. This can be ensured by maintaining a clearance of 1.2 m
to any fixed walls.
ATTENTION!
Do not restrict or block the area around the air intake or outlet.
www.dimplex.de

5.2 Condensed Water Pipe

Condensate that forms during operation must be drained off
frost-free. To ensure proper drainage, the heat pump must be
mounted horizontally. The condensate pipe must have a mini-
mum diameter of 50 mm and must be fed into a sewer in such a
way that it is safe from frost. Do not discharge the condensate di-
rectly into clearing tanks or cesspits, as aggressive vapours or a
condensed water pipe which has not been laid in a frost-free
manner could destroy the evaporator.
ATTENTION!
The frost line can vary according to the climatic region. The regulations
of the countries in question must be observed.
6

Installation

6.1 General Information
The following connections need to be established on the heat
pump:
Flow and return flow of the heating system
Condensate outflow
Control line to the heat pump manager