DHW/group "3"
Coding in the delivered condition
5b:0
DHW cylinder directly
connected to the boiler
5E:0
Circulation pump for cyl-
inder heating stays in
control mode at signal
"External blocking"
5F:0
Circulation pump for cyl-
inder heating stays in
control mode at signal
"External demand"
60:20
During DHW heating, the
boiler water temperature
is max. 20 K higher than
the set DHW tempera-
ture
62:2
Circulation pump with
2 min run-on time after
cylinder heating
63:0
Without auxiliary function
for DHW heating (only for
constant temperature
control units)
65:0
Never adjust!
67:40
For solar DHW heating:
Set DHW temperature
40 °C. Reheating is sup-
pressed above the selec-
ted set temperature
(DHW heating blocked by
the boiler).
6C:100
Set speed, internal circu-
lation pump with DHW
heating 100 %
(cont.)
Possible change
5b:1
DHW cylinder connected
downstream of the low loss
header
5E:1
Circulation pump for cylin-
der heating stops at signal
"External blocking"
5E:2
Circulation pump for cylin-
der heating starts at signal
"External blocking"
5F:1
Circulation pump for cylin-
der heating stops at signal
"External demand"
5F:2
Circulation pump for cylin-
der heating starts at signal
"External demand"
60:5
The difference between the
to
boiler water temperature
60:25
and the set DHW tempera-
ture is adjustable from 5 to
25 K
62:0
Circulation pump without
run-on
62:1
Run-on time adjustable
to
from 1 to 15 min
62:15
63:1
Auxiliary function: 1 x daily
63:2
Every 2 days to every 14
to
days
63:14
63:15
2 x daily
67:0
Set DHW temperature
to
adjustable from 0 to 95 °C
67:95
(limited by boiler-specific
parameters)
6C:0
Set speed adjustable from
to
0 to 100 %
6C:100
Code 2
65