Viessmann VITODENS 200-W Service Instructions Manual page 63

Table of Contents

Advertisement

Boiler/group "2"
Coding in the delivered condition
06:...
Maximum limit of the
boiler water temperature,
specified in °C by the
boiler coding card
07:1
Boiler number in multi
boiler systems (only for
constant temperature
control units)
08:...
Maximum burner output
in kW for a multi boiler
system
0d:0
Never adjust
0E:0
Never adjust
13:1
Never adjust
14:1
Never adjust
15:1
Never adjust
21:0
No service interval (hours
run) selected
23:0
No time interval for
burner service
24:0
No "Service" display
28:0
No burner interval igni-
tion
2E:0
Never adjust
2F:0
Venting program/fill pro-
gram disabled
(cont.)
Possible change
06:20
to
06:127
07:2
to
07:8
08:0
to
08:199
21:1
to
21:100
23:1
to
23:24
24:1
28:1
to
28:24
2F:1
2F:2
Maximum limit of the boiler
water temperature within
the ranges specified by the
boiler
Boiler number 2 to 8 in
multi boiler systems
Maximum burner output
adjustable from 0 to
199 kW (limited by boiler-
specific parameters) in
steps of 1 kW
Number of hours run
before the burner should
be serviced is adjustable
from 100 to 10,000 h
One adjusting step ≙
100 h
Interval adjustable from 1
to 24 months
"Service" display (the
address is automatically
set and must be manually
reset after a service has
been carried out)
Interval adjustable from 1 h
to 24 h. The burner is force-
started once every 30 s
(only when operating with
LPG).
Venting program enabled
Fill program enabled
Code 2
63