Coding in the delivered condition
Weather-compensated/room temperature hook-up
b0:0
With remote control:
Heating mode/reduced
mode: weather-compen-
sated (only for weather-
compensated control
units; change the code
only for the heating circuit
with mixer)
Economy function room temperature
b5:0
With remote control: No
room temperature-
dependent heating circuit
pump logic function (only
for weather-compensa-
ted control units; change
the code only for the heat-
ing circuit with mixer)
Parameter
With heating circuit pump logic function:
address b5:...
Heating circuit pump "OFF"
1
RT
2
RT
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
Coding in the delivered condition
Min. flow temperature heating circuit
C5:20
Electronic minimum flow
temperature limit 20 °C
(only for weather-com-
pensated control units)
> RT
+ 5 K
actual
set
> RT
+ 4 K
actual
set
> RT
+ 3 K
actual
set
> RT
+ 2 K
actual
set
> RT
+ 1 K
actual
set
> RT
actual
set
> RT
- 1 K
actual
set
> RT
- 2 K
actual
set
(cont.)
Possible change
b0:1
Heating mode: weather-
compensated
Reduced mode: with room
temperature hook-up
b0:2
Heating mode: with room
temperature hook-up
Reduced mode: weather-
compensated
b0:3
Heating mode/reduced
mode: with room tempera-
ture hook-up
b5:1
Heating circuit pump logic
to
function, see the following
b5:8
table:
Heating circuit pump "ON"
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
RT
< RT
actual
Possible change
C5:1
Minimum limit adjustable
to
from 1 to 127 °C (limited by
C5:127
boiler-specific parameters)
Code 1
+ 4 K
set
+ 3 K
set
+ 2 K
set
+ 1 K
set
set
- 1 K
set
- 2 K
set
- 3 K
set
49