ERROR CODES

If the thermostat enters an error mode, all outputs are turned off. The thermostat attempts to recover every 10 minutes.
If the error does not clear, use the reset button. This will return all settings back to factory default.
Error code
Message
01
"SENSOR ERROR"
02
03
"RH SENSOR ERROR"
04
"EEPROM ERROR"
05
"SENSOR ERROR"
18
Error Description
Open temperature sensor circuit
Shorted temperature sensor circuit
Invalid response from the RH sensor
Error in permanent memory
All controlling support modules are unresponsive and
the built-in sensor is not used as a backup option
SpECIfICATIONS
Operating: 32° to 120°F (0° to 48.9°C)
Temperature
Shipping: -30° to 150°F (-34.4° to 65.5°C)
Relative humidity
Operating: 5% to 90% R.H. (non-condensing)
Operating voltage
24VAC (18 – 30VAC)
Maximum: 2.5A (total), 1.0A (single output)
Current
Maximum surge current: 5A
Battery back-up
AA size alkaline battery x 2
Outdoor & Remote temperature sensor
Maximum distance: 300 feet
Room temperature measurement
Display range: 32° to 99°F (0° to 40°C)
Outdoor temperature measurement
Display range: -20° to 130°F (-30° to 55°C)
Heat: 40° to 90°F (4° to 32°C)
Setpoint temperature range
Cool: 50° to 99°F (10° to 37°C)
Humidification: 10% to 90% R.H.
Setpoint humidity range
Dehumidification: 10% to 90% R.H.
Environment