not change with units, _F and _C. This can allow one setting to "push" the other to
maintain this difference. When the correct deadband is set, touch SAVE.
Deadband: Adjustable from 0 to 6_
S
Default = 2_
d
6.3.1.3.
Offsets
This option allows calibration (or deliberate miscalibration) of the temperature and
humidity sensors. These offsets are added to the actual temperature/humidity
values. When the correct offsets are made, touch SAVE.
Outdoor temperature: Adjustable from - - 5 to 5_F (- - 3 to 3_C)
S
Default = 0_F
d
Humidity: Adjustable from - - 10 – 10%
S
Default = 0%
d
6.3.1.4.
Reset factory defaults
This option allows the installer to reset certain factory parameters. After the
selections are made, touch SAVE.
Program Schedule: Reset back to pre- - programmed time and temperature.
S
User Settings: Reset user settings back to pre- - programmed values.
S
Install Settings: Reset installation settings back to pre- - programmed values.
S
Last 10 Faults: Reset the last 10 system faults under the Service menu.
S
6.3.1.5.
Scheduling Enable
This option lets the installer allow programming features. After the selection is
made, touch SAVE.
Scheduling: On or Off
S
Default = On
d
29