2.Heat/Cool Deadband; 3.Offsets - Carrier Infinity SYSTXCCWIC01-B Installation Instructions Manual

Hide thumbs Also See for Infinity SYSTXCCWIC01-B:
Table of Contents

Advertisement

6.3.1.2.
Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired
temperatures. The deadband does not change when the user changes between
Fahrenheit (_F) and Celsius (_C). Ex: A 2_ deadband will be 2_F or 2_C and does
not change with units, _F and _C. This can allow one setting to "push" the other to
maintain this difference. When the correct deadband is set, touch SAVE.
Deadband: Adjustable from 0 to 6_
S
Default = 2_
d
6.3.1.3.
Offsets
This option allows calibration (or deliberate miscalibration) of the temperature and
humidity sensors. These offsets are added to the actual temperature/humidity
values. See also Section 6.3.8.2. When the correct offsets are made, touch SAVE. If
the system is non- - zoned, the indoor temperature offset is found on this screen. If
the system is zoned, the indoor temperature offset is found in the Zoning, Offsets
screen.
33