Appendix B: Wiring Diagrams - DSC PC5020 Power864 Installation Manual

Hide thumbs Also See for PC5020 Power864:
Table of Contents

Advertisement

Appendix B: Wi ring Diagrams
B.1 PC5020CF Wiring Diagram (Ground Connection, Zone Circuits)
Battery capacity for standby is
at least 24 hours. Recommended
Battery: DSC model BD7-12.
All terminals Class 2 Power Limited,
except battery leads.
RED
BLK
BATTERY 1
12V 7.0Ah
Maximum battery
charge current
is 360 mA.
For remote station use,
connect PS5350 with 60 hour
battery standby capacity
NOTE: Refer to the Installation Manual
for other AC wiring options.
120VAC
60Hz
PRIMARY
Compatible
signalling device:
Wheelock Model
34T-12-R (UL-Listed)
OBSERVE POLARITY
*
NOTE: AUX+ is shared between AUX+,
Keybus, (Red, Blk, Yel, Grn) and all PGM
outputs. Minimum system required: One
LCD5500Z keypad (85mA) and one
PC5700 (150mA)
or T-Link (150mA).
Available current for AUX+, Keybus &
PGM should total 180mA.
For max. loading, refer to the Battery
Calculation Charts part# 29005057
IMPORTANT: A minimum of 1/4" (7mm)
separation must be maintained at all points
between power limited wiring and all other
non-power limited wiring and connections.
Wire entry for power limited wiring must be
separate from non-power limited wiring.
Non-power
AC IN
limited access
ONLY
WARNING
-
Not to be
removed by anyone except
occupant. This
equipment
should
be
installed
accordance with the National
Fire Code ANSI/NFPA 72
(National
Fire
Protection
Association,
Batterymarch
Park, Quincy MA, 02269).
Printed information describing
proper installation, operation,
testing,
maintenance,
evacuation
planning,
repair service is to be provided
with this equipment. This unit
includes an alarm verification
feature that will result in a
delay of the system alarm
signal
from
the
indicated
circuits.
The
total
(control
unit
plus
smoke
detectors) shall not exceed 60
seconds. No other smoke
detector shall be connected to
these circuits unless approved
by the local authority having
jurisdiction. For compliance
with UL-985, at least one
hardwired smoke detector is
required.
NOTE: For ULC installations, please refer to the ULC Wiring Diagram part#18006238 and the ULC Installation
Information Sheet part#29002157.
PTC
UA186
RED
BLK
Max. Line Resistance
25.7 Ohms
BATTERY 2
Same rating
as Battery 1
+
AC
AUX
BELL
RED
BLK YEL GRN
FTC Frost 3716
16.5VAC 37VA (min)
Do not connect to receptacle
controlled by a switch
Supplementary Bell Circuit
(Supervised for non-fire use only)
BELL / SIREN 12VDC 700 mA MAXIMUM
Power limited access
Power limited access
PC5020 CONTROL PANEL WIRING DIAGRAM
+
-
UA186
+
AC
AUX
BELL
RED
BLK YEL GRN
1
2
PGM
3
4
Z1
COM
Z2
Z3
COM
Z4
Z5
COM
Z6
Z7
COM
Z8
RING TIP R-1 T-1 EGND
16V
AC
37VA
(2)12V 7Ah battery
(not supplied)
Voltage Barrier
INSTALL BATTERY AND AC WIRING AS SHOWN ABOVE
RESISTOR
IDENTIFICATIONS
2-WIRE SMOKE
BELL CIRCUIT
SINGLE ZONE EOL
2200
1000
5%
5%
in
Compatible 2-wire Smoke Detectors
Please see the 2-wire Smoke Detector Compatibility Chart (below) for a
list of 2-wire smoke detectors that have been listed as compatible with the
PC5020CF 2-wire smoke detection zone (PGM2).
Name
Model
Compatibility ID
DSC
MN220 /-R/-T/-RT
PS-220
System
2100AT
A
Sensor
2100TR
A
Sentrol
429AT or 521B/BXT
S09A
SW1 on
400 series,429C, 429CT
S10A
429CRT, 429CSST,
S11A
429CST
521CRXT
S11A
and
521B, 521BXT, SW1 off
S10A
711U/UT, 712U,
S10A
721U/UD/UT
713-5U, 713-6U, 722U
S10A
731U, 731UD, 732U
S11A
Refer to the PC5020/PC5020CF Installation Manual P/N 29005907, Instruction Manual P/N
29005909. The PC5020 is UL Listed for limited energy installations per NEC Article 760.
Recognized limited energy cable should be used. Observe NEC wiring requirements and
local codes defined by the authority having jurisdiction. Printed information describing
proper installation, operation, testing, maintenance, evacuation planning, and repair service
delay
is to be provided with this equipment. Security detection devices that require power from
the control panel must be UL Listed for the intended application and operate over the range
of 10.0 to 14.0 VDC. The DSC Bravo Series is a recommended UL Listed motion detector.
Temperature Range: 0˚C to 49˚C (32˚F to 120˚F)
Maximum Humidity: 85% relative humidity
Control panel is suitable for the following UL installations:
Grade AA Central Station and Grade AA Police Connect with high line security (using T-
Link to communicate to Sur-Gard MLR-IP receiver)
Household Fire and Grade A Household Burglary & Home
Health Care Signaling Equipment
Grade A Local
Grade B Central Station and Grade A Police Connect with basic line security
Grade C Central Station and Grade A Police Connect with basic line security
W
ARNING
PC-Link Connection
Incorrect connections
may result in PTC
WARNING
failure or improper
operation.
High voltage. Disconnect
AC power and telephone
lines prior to servicing.
All zones 6.9VDC nominal (supervised)
COM
1
2
PGM
3
4
Z1
COM
Z2
Z3
Z4
Z5
COM
Z6
Z7
COM
Z8
DEVICE
To +AUX
PGM 1: 50mA Max.*
DEVICE
To +AUX
PGM 2: 300mA Max.(supervised)
DEVICE
To +AUX
PGM 3: 50mA Max.
DEVICE
To +AUX
PGM 4: 50mA Max.
Smoke Detector must be latching type (DSC MN240 Series).
To reset smoke detectors, enter [ ] [7] [2].
Zone Input
Zones 1-8 of PC5020 or
1
PGM 2
+ AUX
Zones 1-4 of PC5700
-
SMOKE DETECTOR
IN
POWER 12VDC
+
LATCHING 4-WIRE SMOKE
DETECTOR (DSC MN240 SERIES)
END OF LINE RESISTOR 5600Ω 0.5W
+
AUX
+ BELL -
RED
BLK
YEL
GRN
1 PGM 2
(-)
2200
END-OF-LINE
RESISTOR
EOLR-3
(+)
Refer to the 2-wire smoke detector compatibility chart in the manual.
LED INDICATOR
5600
5%
+ AUX
1
PGM
2
680
LED
INDICATOR
RESISTOR
(TYPICAL VALUE)
Max #
Base
30
None
30
None
ANY Z
ANY COM
ANY Z
ANY COM
TERMINAL
TERMINAL
TERMINAL
TERMINAL
30
None
30
None
30
None
5600Ω
5600Ω
30
None
NORMALLY CLOSED
NORMALLY OPEN
30
None
CONTACT WITH
CONTACTS WITH
END OF LINE
END OF LINE
30
None
RESISTOR
RESISTOR
30
None
This device complies with Parts 15 and 68 of the FCC rules. Operation is subject to the following two
30
None
conditions: (1) this device may not cause harmful interference, and (2) this device must accept any
30
None
interference received, including interference that may cause undesired operation.
FCC Reg. No.: F53CAN-34330-AL-E REN=0.1B Plug Type: RJ-31X
55
Applicable Standards
SI
SO
UL File No. S5596
UL864 -Control units for fire pro-
tective signaling systems
Listed Services
1. Central Station Fire Monitoring
2. Remote Station Fire Monitoring
GROUND
CONNECTION
Tighten nut to break paint &
make a good connection to
1mA
the cabinet
Nut
Lock washer
Supervised
Nut
Lock washer
Ground wire
from building
Star washer
electrical
Cabinet
installation
Bolt
RING TIP R-1 T-1 EGND
Connect to local phones
To PC5700
Refer to the PC5700 Installation
Fire Module
Instructions Part #29005063
4-WIRE SMOKE DETECTORS
RM-1 POWER LOOP SUPERVISORY RELAY
BLK
WHT
COM
12V
35mA maximum
DC
IN
-
NO
ALM
OUT
ALARM
INITIATING
+
LOOP
RESISTANCE:
OUT
100Ω
WHT
RED
GRN
Refer to installation guidelines in Installation
EOLR-2
Manual & detector manufacturer's literature
when locating smoke detectors.
2-WIRE SMOKE DETECTORS
Compatiblity Identifier: PC5-2
Maximum Operating Voltage: 13.75VDC
Maximum Circuit Resistance: 100Ω (total)
Do not mix different models on the same circuit,
as the correct operation may be impaired.
NOTE: The PC5020 is capable of a maximum of three
2-wire smoke detectors in the alarm condition.
NOTE: For PGM2 only.
PGM CONNECTIONS (1-4)
RELAY OUTPUT
IMPORTANT: Minimum 6.4mm (0.25")
separation must be maintained between
RM-1 circuits and all other wiring.
NOTE: Any device that will sink more than
+ AUX
1
PGM 2
50mA must be connected to PGM2.
RED
BLK
Not for field installations.
DSC
RM-1
WHT YEL
GRN
COM N.C.N.O.
TYPICAL ZONE CIRCUITS
ANY Z
ANY Z
ANY COM
ANY Z
ANY COM
TERMINAL
TERMINAL
TERMINAL
TERMINAL
TERMINAL
ALARM
CONTACT
5600Ω
5600Ω
1 NORMALLY OPEN
2 NORMALLY OPEN
DOUBLE EOL CIRCUIT
CONTACT AND
CONTACT AND
1 NORMALLY CLOSED
1 NORMALLY CLOSED
2 NORMALLY CLOSED
CONTACT WITH
CONTACT WITH
CONTACT WITH
5600Ω END OF LINE
END OF LINE
END OF LINE
RESISTOR
RESISTOR
Made in Canada
(a) The delay (power-up) (start-up) time marked on the
installation wiring diagram of the smoke detector or on the
installed smoke detector(s) is to be used.
ANY COM
TERMINAL
5600Ω
5600Ω
RESISTORS
TABLE 1

Advertisement

Table of Contents
loading

Table of Contents