Checking The Nozzle Pressure - Viessmann VITOGAS 100-F Service Instructions Manual

Rated heating output of 29 to 60 kw gas boiler natural gas and lpg version
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps

Checking the nozzle pressure

A
B
D
C
1. Close the gas shut-off valve.
2. Release the screw inside test nipple
A, but do not remove, then connect
the pressure gauge.
3. Open the gas shut-off valve.
Start the boiler.
4. Check the nozzle pressure.
In case of deviation from the value
in the following table remove pro-
tective cap B.
Adjust the nozzle pressure with
screw C.
Note
Screw D has no function.
10
(cont.)
5. Check the setting values and record
them in the report.
6. Reposition protective cap B.
7. Switch OFF the system ON/OFF
switch on the control unit (the boiler
shuts down).
8. Close the gas shut-off valve.
9. Remove the pressure gauge and seal
test nipple A with screw C.
10. Open the gas shut-off valve, start
the boiler and check test nipple A
for gas tightness.
Danger
Gas escaping from the test
nipple leads to a risk of
explosion.
Check the test nipple for gas
tightness.