Download Print this page

Carrier 59SP5A Installation, Start-Up, Operating And Service And Maintenance Instructions page 58

100 series

Advertisement

g
e. Follow heat value and specific gravity lines to point of in-
tersection to find orifice size and manifold
pressure
setting
for proper
operation.
f. Check
and verify burner
orifice size in furnace.
NEVER
ASSUME
ORIFICE
SIZE.
ALWAYS
CHECK
AND
VERIFY.
NOTE:
For Canadian
altitudes
of 2000
to 4500
ft. (609.6
to
1371.6M),
use
USA
altitudes
of 2001
to 3000
ft. (609.6
to
914.4M).
NOTE:
If orifice
hole appears
damaged
or it is suspected
to have
been
redrilled,
check
orifice
hole
with
a numbered
drill bit of
correct
size.
Never
redrill
an orifice.
A burr-free
and squarely
aligned
orifice
hole is essential
for proper flame characteristics.
g. Replace
orifice with correct
size, if required
by Table 20.
Use only factory-supplied
orifices.
See EXAMPLE
1.
EXAMPLE
1:0 - 2000 ft. (0 - 609.6M)
altitude
Heating
value = 1050 Btu/cu ft.
Specific
gravity
= 0.62
Therefore:
Orifice No. 44
Manifold
pressure:
3.4-in.
w.c.
* Furnace
is shipped
with No. 44 orifices. In this example,
all main
burner orifices
are the correct
size and do not need to be changed
to
obtain proper
input rate.
1. Adjust manifold
pressure
to obtain input rate. (See Fig. 51.)
a. Turn gas valve ON/OFF
switch to OFF.
b. Remove
manifold
pressure
tap plug from gas valve.
c. Connect
a water column
manometer
or similar
device to
manifold
pressure
tap.
d. Turn gas valve ON/OFF
switch to ON.
e. Manually
close blower
door switch.
f. Jumper
R and W thermostat
connections
on control to start
furnace.
(See Fig. 35.)
g. Remove
regulator
adjustment
cap from gas valve pressure
regulator
(See Fig. 51.) and turn adjusting
screw (3/16 or
smaller flat-tipped
screwdriver)
counterclockwise
(out) to
decrease
input rate or clockwise
(in) to increase
input rate.
NOTE:
DO NOT
set manifold
pressure
less than 3.2-in.
w.c. or
more
than
3.8 in. w.c. for natural
gas.
If manifold
pressure
is
outside
this range,
change
main burner
orifices to obtain
manifold
pressure
in this range.
h. When correct input is obtained,
replace
cap that conceals
gas valve regulator
adjustment
screws.
Main burner flame
should be clear blue, almost transparent
(See Fig. 59.)
i. Remove
jumper
R to W.
2. Verify natural
gas input rate by clocking
meter.
a. Turn off all other gas appliances
and pilots served
by the
meter.
b. Jumper
R to W.
c. Run furnace
for 3 minutes.
d.
Measure
time (in sec) for gas meter to complete
1 revolu-
tion and note reading.
The 2 or 5 cubic feet dial provides
a more accurate
measurement
of gas flow.
e. Refer to Table 19 for cubic ft. of gas per hr.
f. Multiply
gas rate cu fl./hr by heating
value (Btuh/cu
ft.)
to obtain input. If clocked
rate does not match required
in-
put from Step 1, increase manifold
pressure
to increase in-
put or decrease manifold
pressure to decrease input. Repeat
steps b through e until correct
input is achieved.
Re-install
regulator
seal cap on gas valve.
Adjust
Temperature
Rise
NOTE:
Blower
door must
be installed
when
taking
temperature
rise
reading.
Leaving
blower
door
off will
result
in incorrect
temperature
measurements.
FURNACE
OVERHEATING
HAZARD
Failure to follow this caution
may result in shortened
furnace life.
Set air temperature rise within limits specified on the rating
plate to prevent reduced life of furnace components.
FURNACE
DAMAGE
HAZARD
Failure to follow
this caution
may result in overheating
the
heat exchangers
or condensing
flue gases in heat exchanger
areas not designed
for condensate.
Temperature
rise must
be within
limits
specified
on unit
rating plate.
[]NIT
DAMAGE
HAZARD
Failure to follow this caution
may result in component
damage,
Temperature rise must be within limits specified on furnace
rating plate. Recommended
operation is at midpoint of rise
range or slightly above,
This
furnace
must
operate
within
the
temperature
rise
ranges
specified
on the furnace
rating plate. Determine
the air temperature
as follows:
a. Place duct thermometers
in return and supply ducts as close
to furnace as possible.
Be sure thermometers
do not "see"
heat
exchangers
so that
radiant
heat does
not
affect
thermometer
readings.
This is particularly
important
with
straight
run ducts.
b. When thermometer
readings
stabilize,
subtract
return-air
temperature
from
supply-air
temperature
to determine
temperature
rise.
If the temperature
rise is outside
this range,
check the following:
a. Gas input for gas heat operation.
b. Derate for altitude
if applicable.
c. Return
and supply ducts for excessive
restrictions
causing
static pressures
greater
than 0.50-in.
w.c.
d. Adjust
temperature
rise by adjusting
blower
speed.
• Increase
blower
speed to reduce temperature
rise.
• Decrease
blower
speed to increase
temperature
rise.
58

Advertisement

loading