6.1 General

Have an authorized distributor/dealer install the
generator set outdoors according to the instructions in
this section. Do not install this generator set indoors.
The generator set installation must comply with state
and local code requirements.
Use the specifications provided here only in the initial
planning. Use the generator set and transfer switch
spec sheets, dimension drawings, and wiring diagrams
for installation.
Contact an authorized service
distributor/dealer for the most current information.

6.2 Weight

WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
The generator set weighs approximately 186 kg
(410 lb.). Use lifting bars inserted through the holes in
the skid to lift the unit. See Figure 6-1 for lifting hole
locations.

6.3 Generator Set Inspection

Complete a thorough inspection of the generator set.
Check for the following:
1. Inspect the generator set for loose or damaged
parts or wires. Repair or tighten any loose parts
before installation.
2. Check the engine oil. Fill, if necessary, with the
recommended make and grade of oil.
Section 3.3.3 for engine oil recommendations.
TP-6195 1/04

6.4 Mounting

Install the generator set outdoors. Maintain a minimum
clearance of 0.9 m (3 ft.) from any building as shown in
Figure 6-1.
Do not install the generator set where
exhaust gas could accumulate and seep inside or be
drawn into a potentially occupied building. Mount the
generator set so that the hot exhaust does not blow on
plants or other combustible materials.
See Figure 6-1 for the generator set dimensions and
fuel and electric inlet locations.
dimensions are shown in millimeters, with inches in
brackets.
The generator set is shipped on a plastic mounting pad.
Prepare a flat, level mounting area covered with gravel
or compacted soil. Set the plastic mounting pad directly
on the gravel or compacted soil. Do not install the
mounting pad directly on the grass.

6.5 Exhaust Requirements

Carbon monoxide.
Can
fainting, or death.
The
leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause
severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause
death if inhaled for even a short time. Avoid breathing exhaust
fumes when working on or near the generator set. Never
operate the generator set inside a building. Never operate the
generator set where exhaust gas could seep inside or be
drawn into a potentially occupied building through windows, air
intake vents, or other openings.
The exhaust system is complete for generator sets
installed outdoors. Do not install this generator set
indoors.
See

Section 6 Installation

WARNING
cause
severe
nausea,
exhaust
system
must
Section 6 Installation
The drawing
be
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

12res

Table of Contents