Using Flexible Vent Components - Napoleon GD36NTR Installation And Operation Instructions Manual

Direct vent millivolt system
Table of Contents

Advertisement

USING FLEXIBLE VENT COMPONENTS

"Wolf Steel Approved Venting" as identified by the
stamp only on the 7" outer liner.
The vent system must be supported ap-
proximately every 3 feet for both vertical
HORIZONTAL AIR TERMINAL INSTALLATION
1. Cut or frame a hole in an exterior wall with a minimum
round or square opening of 10½ inches. Secure the firestop
spacer over the opening to the interior wall.
2. Stretch the 4" diameter aluminum flexible liner to the
required length taking into account the additional length
needed for the finished wall surface. Slip the liner a mini-
mum of 2" over the inner sleeve of the air terminal and
secure with 3 #8 screws. Apply a heavy bead of the high
temperature sealant (not supplied).
3. Using the 7" diameter flexible aluminum liner, slide
over the outer combustion air sleeve of the air terminal and
secure with 3 #8 screws. Seal as before.
FIGURE 27
The air terminal mounting plate may be recessed into
the exterior wall or siding by 1½", the depth of the return
flange.
For safe and proper operation of the fireplace, follow the
venting instructions exactly.
All inner exhaust and outer intake vent pipe joists may
be sealed using either Red RTV high temp silicone seal-
ant or Black high temp Mill Pac with the exception of the
fireplace exhaust flue collar which must be sealed us-
ing Mill Pac (not supplied).
4. Insert the liners through the firestop maintaining the
required clearance to combustibles. Holding the air termi-
nal (lettering in an upright, readable position), secure to
the exterior wall and make weather tight by sealing with
caulking (not supplied).
5. Apply a heavy bead of the high temperature sealant to
the inside of the 4" liner approximately 1" from the end. Slip
the liner a minimum of 2" over the fireplace vent collar and
secure with 3 #8 screws.
6. Using the 7" diameter flexible aluminium liner, apply
sealant, slide a minimum of 2" over the fireplace combus-
tion air collar and secure with 3 #8 screws.
7. If more liner needs to be used to reach the fireplace,
couple them together as illustrated. The vent system must
be supported approximately every 3 feet for both vertical
and horizontal runs. Use noncombustible strapping to
maintain the minimum 1" clearance to combustibles.
VERTICAL AIR TERMINAL INSTALLATION
tion or the optional roof support.
2. Stretch the 4" diameter aluminium flexible liner to the
required length. Slip the liner a minimum of 2" over the
inner sleeve of the air terminal and secure with 3 #8 screws.
Seal using a heavy bead of the
high temperature sealant.
3. Repeat using 7" diameter
aluminium flexible liner.
4. Thread the air terminal pipe
assembly down through the roof.
The air terminal must be located
vertically and plumb. Attach the
FIGURE 28
air terminal assembly to the roof
support, ensuring that a mini-
mum 16" of air terminal will pen-
etrate the roof when fastened.
DO NOT CLAMP THE FLEXIBLE ALUMINIUM LINER.
FIGURE 29
1. Fasten the roof support
to the roof using the
screws provided. The roof
support is optional. In this
case the venting is to be
adequately supported us-
ing either an alternate
method suitable to the
authority having jurisdic-
W415-0210 / G / 12.10.04
17