Ras-18Nkpx-T / Ras-18N2Ax-T - Toshiba RAS-24NKHP-E Service Manual

Table of Contents

Advertisement

5-8. RAS-18NKPX-T / RAS-18N2AX-T

0.39 m
(Connecting pipe)
∅15.88
O.D.:15.88 mm
P
Packed valve
(∅15.88)
Accumulator
Compressor
PH290X2C-4FT1
50 Hz
Standard
Cooling
High temperature
Low temperature
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Indoor unit
Evaporator
Cross flow fan
Condenser
Propeller fan
Outdoor unit
Standard
Surface temp. of heat
exchanger interchanging
pressure P
(MPaG)
pipe T (°C)
0.52
0.62
0.38
− 16 −
FILE NO. SVM-06009
T
Packed valve
(∅6.35)
Capillary tube
∅2.0x1000 s
Refrigerant
R22 1.50 kg
Mark (
) means check points of Gas Leak
Fan speed
(indoor)
11.0
High
14.7
High
3.0
Low
0.49 m
(Connecting pipe)
∅6.35
O.D.:6.35 mm
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
27/19
35/24
32/23
43/26
21/15
21/15