Hand/Auto macro

This macro can be used when switching between two external control devices is
needed. To enable the macro, set the value of parameter
For the parameter default values, see section
on page 142. If you use other than the default connections presented below, see
section
Note: Parameter

Default I/O connections

1...10 kohm
max. 500 ohm
1)
360 degree grounding under a clamp.
I/O terminals
on page 40.
2108
START INHIBIT must remain in the default setting 0 (OFF).
X1A
1
SCR
2
AI1
3
GND
4
+10V
5
AI2
6
GND
7
AO
8
GND
1)
9
+24V
10
GND
11
DCOM
12
DI1
13
DI2
14
DI3
15
DI4
16
DI5
X1B
17
ROCOM
18
RONC
19
RONO
20
DOSRC
21
DOOUT
22
DOGND
Default values with different macros
Signal cable shield (screen)
Motor speed reference (Hand): 0...10 V
Analog input circuit common
Reference voltage: +10 VDC, max. 10 mA
Motor speed reference (Auto): 4...20 mA
Analog input circuit common
Motor speed value: 0...20 mA
Analog output circuit common
Auxiliary voltage output: +24 VDC, max. 200 mA
Auxiliary voltage output common
Digital input common
Stop (0) / Start (1) (Hand)
Forward (0) / Reverse (1) (Hand)
Hand (0) / Auto (1) control selection
Forward (0) / Reverse (1) (Auto)
Stop (0) / Start (1) (Auto)
Relay output
No fault [Fault (-1)]
Digital output, max. 100 mA
No fault [Fault (-1)]
2)
The signal source must be powered externally.
See the manufacturer's instructions. An
example of a connection using a two-wire
sensor is given on page 41.
Tightening torque = 0.5 N·m / 4.4 lbf. in.
9902
to 5 (HAND/AUTO).
2)
Application macros
91