Parameters – complete descriptions
Parameters – complete descriptions
Index Name/Selection

10 START/STOP/DIR

1001
EXT1 COMMANDS
NOT SEL
DI1
DI1,2
DI1P,2P
DI1P,2P,3
DI1P,2P,3P
KEYPAD
DI1F,2R
COMM
TIMED FUNC 1
TIMED FUNC 2
TIMED FUNC 3
TIMED FUNC 4
DI5
Description
The sources for external start, stop and direction control
Defines the connections and the source for the start, stop and direction
commands for external control location 1 (EXT1).
No start, stop and direction command source
Start and stop through digital input DI1. 0 = stop, 1 = start. Direction is fixed
according to parameter
1003
Start and stop through digital input DI1. 0 = stop, 1 = start. Direction through
digital input DI2. 0 = forward, 1 = reverse. To control direction, parameter
1003
DIRECTION setting must be REQUEST.
Pulse start through digital input DI1. 0 -> 1: Start. (In order to start the drive,
digital input DI2 must be activated prior to the pulse fed to DI1.)
Pulse stop through digital input DI2. 1 -> 0: Stop. Direction of rotation is fixed
according to parameter
1003
Pulse start through digital input DI1. 0 -> 1: Start. (In order to start the drive,
digital input DI2 must be activated prior to the pulse fed to DI1.)
Pulse stop through digital input DI2. 1 -> 0: Stop. Direction through digital
input DI3. 0 = forward, 1 = reverse. To control direction, parameter
DIRECTION setting must be REQUEST.
Pulse start forward through digital input DI1. 0 -> 1: Start forward. Pulse start
reverse through digital input DI2. 0 -> 1: Start reverse. (In order to start the
drive, digital input DI3 must be activated prior to the pulse fed to DI1/DI2).
Pulse stop through digital input DI3. 1 -> 0: Stop. To control the direction,
parameter
1003
DIRECTION setting must be REQUEST.
Start, stop and direction commands through control panel when EXT1 is
active. To control the direction, parameter
REQUEST.
Start, stop and direction commands through digital inputs DI1 and DI2.
DI1
DI2 Operation
0
0
Stop
1
0
Start forward
0
1
Start reverse
1
1
Stop
Parameter
1003
DIRECTION setting must be REQUEST.
Fieldbus interface as the source for the start and stop commands, i.e. control
word
0301
FB CMD WORD 1 bits 0...1. The control word is sent by the
fieldbus controller via the fieldbus adapter or embedded fieldbus (modbus) to
the drive. For the control word bits, see section
on page 262.
Timed start/stop control. Timed function 1 active = start, timed function 1
inactive = stop. See parameter group
See selection TIMED FUNC 1.
See selection TIMED FUNC 1.
See selection TIMED FUNC 1.
Start and stop through digital input DI5. 0 = stop, 1 = start. Direction is fixed
according to parameter
1003
DIRECTION (setting REQUEST = FORWARD).
DIRECTION (setting REQUEST = FORWARD).
1003
DIRECTION setting must be
DCU communication profile
36 TIMED
FUNCTIONS.
DIRECTION (setting REQUEST = FORWARD).
Def, FbEq
DI1,2
0
1
2
3
4
1003
5
8
9
10
11
12
13
14
20
Actual signals and parameters
159