Parameters – complete descriptions
Index Name/Selection
3505
AO EXCITATION
DISABLE
ENABLE

36 TIMED FUNCTIONS

3601
TIMERS ENABLE
NOT SEL
DI1
DI2
DI3
DI4
DI5
ACTIVE
DI1(INV)
DI2(INV)
DI3(INV)
DI4(INV)
DI5(INV)
3602
START TIME 1
00:00:00...23:59:58
3603
STOP TIME 1
00:00:00...23:59:58
3604
START DAY 1
MONDAY
TUESDAY
WEDNESDAY
THURSDAY
FRIDAY
SATURDAY
SUNDAY
3605
STOP DAY 1
See parameter 3604.
3606
START TIME 2
3607
STOP TIME 2
Description
Enables current feed from analog output AO. Parameter setting overrides
parameter group
15 ANALOGUE OUTPUTS
With PTC the output current is 1.6 mA.
With Pt 100 the output current is 9.1 mA.
Disabled
Enabled
Time periods 1 to 4 and booster signal. See section
page 131.
Selects the source for the timed function enable signal.
Timed function is not selected.
Digital input DI. Timed function enable by a rising edge of DI1.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
Timed function is always enabled.
Inverted digital input DI1. Timed function enable by a falling edge of DI1.
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
See selection DI1(INV).
Defines the daily start time 1. The time can be changed in 2 second steps.
hours:minutes:seconds. Example: If parameter value is set to 07:00:00, the
timed function is activated at 7:00 (7 a.m).
Defines the daily stop time 1. The time can be changed in 2 second steps.
hours:minutes:seconds. Example: If parameter value is set to 18:00:00, the
timed function is deactivated at 18:00 (6 p.m).
Defines the start day 1.
Example: If parameter value is set to MONDAY, timed function 1 is active
from Monday midnight (00:00:00).
Defines the stop day 1.
If parameter is set to FRIDAY, timed function 1 is deactivated on Friday
midnight (23:59:58).
See parameter
3602
START TIME 1.
See parameter
3602
START TIME 1.
See parameter
3603
STOP TIME 1.
See parameter
3603
STOP TIME 1.
settings.
Timed functions
on
Actual signals and parameters
211
Def, FbEq
DISABLE
0
1
NOT SEL
0
1
2
3
4
5
7
-1
-2
-3
-4
-5
00:00:00
00:00:00
MONDAY
1
2
3
4
5
6
7
MONDAY