Parameters – complete descriptions
Index Name/Selection

32 SUPERVISION

3201
SUPERV 1 PARAM
Description
Signal supervision. Supervision status can be monitored with relay or
transistor output. See parameter groups
IN & TRAN
OUT.
Selects the first supervised signal. Supervision limits are defined by
parameters
3202
SUPERV 1 LIM LO and
Example 1: If
3202
SUPERV 1 LIM LO <
Case A =
1401
RELAY OUTPUT 1 value is set to SUPRV1 OVER. Relay
energises when value of the signal selected with
exceeds the supervision limit defined by
remains active until the supervised value drops below the low limit defined by
3202
SUPERV 1 LIM LO.
Case B =
1401
RELAY OUTPUT 1 value is set to SUPRV 1 UNDER. Relay
energises when value of the signal selected with
drops below the supervision limit defined by
relay remains active until the supervised value rises above the high limit
defined by
3203
SUPERV 1 LIM HI.
Value of supervised parameter
HI (par. 3203)
LO (par. 3202)
Case A
Energized (1)
0
Case B
Energized (1)
0
Example 2: If
3202
SUPERV 1 LIM LO >
The lower limit
3203
SUPERV 1 LIM HI remains active until the supervised
signal exceeds the higher limit
limit. The new limit remains active until the supervised signal drops below the
lower limit
3203
SUPERV 1 LIM HI, making it the active limit.
Case A =
1401
RELAY OUTPUT 1 value is set to SUPRV1 OVER. Relay is
energized whenever the supervised signal exceeds the active limit.
Case B =
1401
RELAY OUTPUT 1 value is set to SUPRV1 UNDER. Relay is
de-energized whenever the supervised signal drops below the active limit.
Value of supervised parameter
LO (par. 3202)
HI (par. 3203)
Case A
Energized (1)
0
Case B
Energized (1)
0
14 RELAY OUTPUTS
3203
SUPERV 1 LIM HI.
3203
SUPERV 1 LIM HI
3201
SUPERV 1 PARAM
3203
SUPERV 1 LIM HI. The relay
3201
SUPERV 1 PARAM
3202
SUPERV 1 LIM LO. The
3203
SUPERV 1 LIM HI
3202
SUPERV 1 LIM LO, making it the active
Active limit
Def, FbEq
and
18 FREQ
103
t
t
t
t
t
t
Actual signals and parameters