Outside Air Kit Installation - Quadra-Fire Adventure-III Installation Manual

Hide thumbs Also See for Adventure-III:
Table of Contents

Advertisement

D. Outside Air Kit Installation
A source of air (oxygen) is necessary in order for combustion
to take place. Whatever combustion air is consumed by the
fire must be replaced.
Air is replaced via air leakage around windows and under
doors. In homes that have tightly sealed doors and windows,
an outside air source is highly recommended. An optional
Outside Air Kit (OAK-ADV) is available.
Included in kit: Termination cap, (2) wire ties, pedestal
coverplate, flex adapter, and fasteners. See Figure 5.9.
Figure 5.9
Items Needed for Installation (not supplied)
• 4 inch flex aluminum pipe, or if using alternate material,
then it shall be made from durable, non-combustible, heat
resistant material up to 350
the required length for your installation.
• Phillips head screwdriver
• Silicone sealant
• Drills and saws necessary for cutting holes through the
wall or flooring in your home
For Wall Installation
1. Remove materials from carton.
2. Using a #2 Philips screwdriver, remove the pedestal
screen cover from the rear of the pedestal and replace
with the Outside Air Cover Plate. See Figure 5.3.
3. Attach the flex adapter to the plate with the screws pro-
vided.
4. Cut a 4 1/4 inch hole in the outside wall or floor to accom-
modate the outside air duct. Use 4 inch duct to directly
connect the appliance to the inlet air hood supplied. Seal
between the wall and duct with silicone to prevent mois-
ture and cold air infiltration.
Quadra-Fire • Adventure-III Installation Manual • 4083-901 • Rev B • 05/15
o
o
F (177
C). Cut the pipe to
For Floor Installation
1. Remove the pedestal screen cover from the rear of the
pedestal
2. Remove the cover plate on the pedestal base and install
it on the Outside Air Cover Plate.
3. Cut a 4 ¼ inch hole in the floor to accommodate the
outside air duct. Use rigid 4 inch tube to go through the
pedestal base and floor. Termination must have a rodent
screen or use the supplied termination cap.
4. Install the Outside Air Cover Plate
Fire Risk.
Asphyxiation Risk.
Do not draw outside combustion air from:
• Wall, floor or ceiling cavity
• Enclosed space such as an attic or garage
• Close proximity to exhaust vents or chimneys
Fumes or odor may result
Asphyxiation Risk.
Outside air inlet must be located to prevent blockage
from:
Leaves
Snow or ice
Other debris
Block may cause combustion air starvation
Smoke spillage may set off alarms or irritate sensitive individu-
als.
WARNING
Asphyxiation Risk.
Length of outside air supply duct shall NOT exceed the
length of the vertical height of the exhaust flue.
• Fire will not burn properly
• Smoke spillage occurs when door is opened due to air star-
vation.
WARNING
WARNING
21

Advertisement

Table of Contents
loading

Table of Contents