F. Masonry Chimney
Figure 4.7
WARNING
Fire Risk.
Follow Chimney Connector Manufacturer's
Instructions for Proper Installation.
ONLY use connector:
• Within the room, between appliance and ceiling or wall.
Connector shall NOT pass through:
• Attic or roof space
• Closet or similar concealed space
• Floor or ceiling
Maintain minimum clearances to combustibles
Quadra-Fire • Adventure-III Installation Manual • 4083-901 • Rev B • 05/15
Spark Arrestor Cap
Concrete Cap
1 in. (25mm) Clearance
With Firestop
Ceiling Joist
Combustible Wall
Thimble,
12 in. (305mm)
Of Brick
24" Min.
Floor
Protector
Fireclay Flue Liner
With Air Space
Rafter
Flashing
Sheathing
Outside Air Rear Vent
Outside Air
Termination Cap
Fire Risk.
When lining air-cooled factory-built chimneys:.
• Run chimney liner approved to UL 1777 Type HT
requirements (2100 degrees F)
• Re-install original factory built chimney cap ONLY
• DO NOT block cooling air openings in chimney
• Blocking cooling air will overheat the chimney
Eave
Airtight
Cleanout Door
WARNING
15