Electrical Service Guide For 240 Vac; Extension Cord Data - Miller Electric 375 X-TREME User Manual

Air plasma cutting and gouging
Hide thumbs Also See for 375 X-TREME:
Table of Contents

Advertisement

4-8. Electrical Service Guide For 240 VAC

Y
CAUTION:
INCORRECT INPUT POWER can damage this welding power source. This welding power
source requires a CONTINUOUS supply of 60 Hz (+10%) power at +10% of rated input voltage. Phase
to ground voltage shall not exceed +10% of rated input voltage. Do not use a generator with automatic
idle device (that idles engine when no load is sensed) to supply input power to this welding power
source.
NOTE
Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Rating In Amperes
Circuit Breaker
Min Input Conductor Size In AWG
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG
Reference: 2005 National Electrical Code (NEC) (including article 630)
1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 "Time-Delay" fuses are UL class "RK5" .
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amp), and UL class "H" ( 65 amp and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
Y Caution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard. These
recommendations are for a dedicated branch circuit that applies to the rated output and duty cycle of the welding power source.

4-9. Extension Cord Data

NOTE
Input Power
Phase
Input Voltage
120 V
1
240 V
1
OM-225 216 Page 12
.
A complete Parts List is available at www.MillerWelds.com
Actual input voltage should not exceed 10% of indicated required input voltage. If
actual input voltage is outside of this range, output may not be available.
1
2
, Time-Delay
3
Normal Operating
4
4
When calculating max. cord length, remember to include conductor length from
line disconnect device to input power receptacle.
Hertz
60
60
Conductor Size
14 AWG
14 AWG
60 Hz
Single
Phase
240
13.9
15
20
14
91
(28)
14
Max. Cord Length
22 ft (7 m)
91 ft (28 m)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ice-27tSpectrum 375 x-treme

Table of Contents