Baxi Combi 130 HE Installation & Servicing Instructions Manual page 37

Gas fired wall mounted condensing combination boiler
Table of Contents

Advertisement

Facia Box
Fig. 61
Pump
Pump
Head
Plug Connector
Pump Electrical
Cover
Facia Securing
Screws
Pump Setting
Hydraulic
Manifold
Wiring
Harness
Fig. 63
Fig. 64
13.0 Changing Components
The pump, 3-way diverter valve, pressure
gauge, pressure relief valve, plate heat
exchanger and DHW flow switch can be
accessed after hinging down the facia box.
1. Release the facia securing screws (
and hinge down the facia box (Fig. 61).
13.7
1. If only the head needs replacing, a standard
Grundfos UPS 15-60 pump head is
interchangeable (see section 13.9 for details).
2. This must be switched to setting N
13.8
1. Drain the boiler
2. Unplug the wiring harness from the pump.
3. Remove the four screws retaining the pump
backplate to the hydraulic manifold.
NOTE: Ensure nuts are not dislodged.
4. Remove the pump.
5. Fit the new pump and reassemble in reverse
order.
13.9
Fig. 62
1. Drain the boiler
2. Unplug the wiring harness from the pump.
3. Remove the four socket head screws securing
the pump head and separate it from the housing.
4. Remove the screws retaining the pump
electrical covers on the original and replacement
heads.
5. From the replacement UPS 15-60 pump head
remove the strain relief cable gland and discard.
6. Remove the plug connector from the old pump
head and wire it into the UPS 15-60 pump head.
7. Replace the electrical cover to the new pump
head and assemble with the electrical box at
6 o'clock to the housing.
8. Check that the pump has been switched to
setting N
harness plug.
Pump (Fig. 61)
o
Pump (Complete)
(Fig. 63)
(see Section 13.1 paragraph 2 & 3).
Pump (Head Only) (Fig. 64)
(see Section 13.1 paragraph 2 & 3).
o
3 (Fig. 62) and reconnect the wiring
1
/
turn)
4
3 (Fig. 62).
37