Electrical - Accessories; Water Valve Wiring - Carrier 50YER036 Installation, Operation And Maintenance Instructions

Gt-pw water-to-water series
Table of Contents

Advertisement

Accessory Connections
A terminal paralleling the compressor contactor coil has been
provided on the CXM control. Terminal "A" is designed to
control accessory devices, such as water valves. Note: This
terminal should be used only with 24 Volt signals and not
line voltage. Terminal "A" is energized with the compressor
contactor. See Figure 5 or the specific unit wiring diagram for
details.
Figure 5: Accessory Wiring
Water Solenoid Valves
An external solenoid valve(s) should be used on ground
water installations to shut off flow to the unit when the
compressor is not operating. A slow closing valve may be
required to help reduce water hammer. Figure 5 shows
typical wiring for a 24VAC external solenoid valve. Figures
6 or 7 illustrate typical slow closing water control valve
wiring for Taco 500 series (ClimateMaster P/N AVM...)
and Taco SBV series valves. Slow closing valves take
approximately 60 seconds to open (very little water will flow
before 45 seconds). Once fully open, an end switch allows
the compressor to be energized. Only relay or triac based
electronic thermostats should be used with slow closing
valves. When wired as shown, the slow closing valve will
operate properly with the following notations:
1. The valve will remain open during a unit lockout.
2. The valve will draw approximately 25-35 VA through the
"Y" signal of the thermostat.
Note: This valve can overheat the anticipator of an
electromechanical thermostat. Therefore, only relay or
triac based thermostats should be used.
W a t e r- t o - W a t e r ( 5 0 Y E R ) S e r i e s - P u r o n
Electrical - Low Voltage Wiring
Figure 6: AVM Valve Wiring
1
Heater Switch
Thermostat
Figure 7: Taco SBV Valve Wiring
Unidad Empacada
1
Calentador Interruptor
Termostato
R e v. : 1 J u l y, 2 0 1 0
2
AVM
3
Taco Valve
2
AVM
3
Taco Válvula
®
19