Haier AB36NACBEA Service Manual page 112

4hp 5hp universal outdoor unit air conditioning
Hide thumbs Also See for AB36NACBEA:
Table of Contents

Advertisement

wired control.
J2,SW3-2——function selection-temperature compensation in heating mode:
1means "yes", 0means "no".
J3,SW3-3——function selection-outdoor communication: 1means "yes", 0means
"no". This PCB must be 1.
J4,SW3-4——function selection-heat pump unit: 1means "heat pump", 0means
"cooling only".
1/60——test in short circuit, but in operation short circuit mustn't be permitted.
CHECK — — short spring switch control, it also can be used as switch of
convertible type except for testing.
J5,SW4-1——function selection-elevating function: 1means "yes", 0means "no".
J6,SW4-2——function selection –health function: 1means common (indoor fan
motor running); 0 means special (indoor, outdoor running).
J7,SW5-1——function selection –swing mode: 1 means common(simultaneous
motor), 0 means special (swing motor).
J8,SW5-2——function selection – system combination: 1means fixed frequency
single unit, 0 means fixed frequency multi split.
J9,SW5-3——function selection –group control: 1 stands for the master unit (its
address in wired controller is 0), 0 stands for the slave units (the address should be
set by the dip switch, their addresses only can be in the range: 1~15)
J10,SW5-4——function selection –preset: 1 no meaning, 0 no meaning