S-0-0390
P-0-1300
S-0-0095
F2013
D319
D319: temperature of
leakage very high
F2013
D322
D322: fuse -11F4
tripped
F2013
D323
D323: error oil level
sensor on port 1
F2013
D327
D327: return flow
filter contamination
very high
F2013
D700
D700: user config
input err, P-0-1389 (...)
Cause
The monitoring of the leakage
temperature indicates an
alarm.
P-0-1294 > P-0-1389[48]
The monitoring of the digital
feedback signal of the sensor
supply fuse indicates an alarm.
P-0-1400.2 = P-0-1380.5
• The oil level sensor on IO link
port 1 is no longer available.
• An error has occurred at the
sensor.
• An incorrect sensor
(vendor/device ID) is
connected to IO link port 1.
The monitoring of the return
flow filter indicates an alarm.
P-0-1283 > P-0-1389[34]
The configuration of the device
data (e.g. threshold value)
cannot be implemented.
Product information 47/128
Remedy
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Check the oil cooling pump.
▶
Check the water cooling unit.
▶
Check the pump and replace it, if necessary.
▶
Check fuse -11F4.
▶
Check the configuration of the signal logic
(NO / NC).
▶
Check the flashlight.
▶
Check the connection and function of the oil
level sensor (if the sensor is no longer needed,
reset and restart the MLD program).
▶
Remove the faulty sensor.
▶
Check the connection of the oil level sensor on
the basis of the electrical circuit diagram.
▶
Check the limit value.
▶
Check the sensor output signal.
▶
Replace the return flow filter.
▶
Check the editable inputs (for details see text).
▶
Reset the configuration to factory settings.