S-0-0390
P-0-1300
S-0-0095
F2013
D319
D319: temperature of
leakage very high
F2013
D322
D322: fuse -11F4
tripped
F2013
D323
D323: error oil level
sensor on port 1
F2013
D327
D327: return flow
filter contamination
very high
F2013
D700
D700: user config
input err, P-0-1389 (...)
Cause
The monitoring of the leakage
temperature indicates an
alarm.
P-0-1294 > P-0-1389[48]
The monitoring of the digital
feedback signal of the sensor
supply fuse indicates an alarm.
P-0-1400.2 = P-0-1380.5
• The oil level sensor on IO link
port 1 is no longer available.
• An error has occurred at the
sensor.
• An incorrect sensor
(vendor/device ID) is
connected to IO link port 1.
The monitoring of the return
flow filter indicates an alarm.
P-0-1283 > P-0-1389[34]
The configuration of the device
data (e.g. threshold value)
cannot be implemented.
Product information 47/128
Remedy
Check the limit value.
Check the sensor output signal.
Check the oil cooling pump.
Check the water cooling unit.
Check the pump and replace it, if necessary.
Check fuse -11F4.
Check the configuration of the signal logic
(NO / NC).
Check the flashlight.
Check the connection and function of the oil
level sensor (if the sensor is no longer needed,
reset and restart the MLD program).
Remove the faulty sensor.
Check the connection of the oil level sensor on
the basis of the electrical circuit diagram.
Check the limit value.
Check the sensor output signal.
Replace the return flow filter.
Check the editable inputs (for details see text).
Reset the configuration to factory settings.